Setting Cooling Temperature Setpoint 1; Setting The Outside Air Temperature 1; Setting Cooling Temperature Setpoint 2; Setting The Outside Air Temperature 2 - AERMEC MODUCONTROL Manuel D'utilisation

Masquer les pouces Voir aussi pour MODUCONTROL:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

MIN
Index - String
value
-20 °C
MIN
Index - String
value
-40 °C
MIN
Index - String
value
-20 °C
MIN
Index - String
value
-40 °C
Value
Index - string
MIN
25 °C
MIN
Index - String
value
-40 °C
Parameter visible ONLY on units suitable for the production
of hot water
Parameter visible ONLY on units suitable for the production
of DHW

Setting cooling temperature setpoint 1

MAX
value
This parameter indicates the maximum value of the cooling setting, corresponding with the minimum
26 °C
outside air temperature (index (7) user menu). This parameter is only visible if the compensation fun-
ction has been activated (index (5) user menu).

Setting the outside air temperature 1

MAX
value
This parameter indicates the minimum outside air temperature taken into consideration for cooling
50 °C
compensation. This parameter is only visible if the compensation function has been activated (index (5)
user menu).

Setting cooling temperature setpoint 2

MAX
value
This parameter indicates the minimum value of the cooling setting, corresponding with the maximum
26 °C
outside air temperature (index (9) user menu). This parameter is only visible if the compensation fun-
ction has been activated (index (5) user menu).

Setting the outside air temperature 2

MAX
value
This parameter indicates the maximum outside air temperature taken into consideration for cooling
50 °C
compensation. This parameter is only visible if the compensation function has been activated (index (5)
user menu).

Setting heating set 1

Value
MAX
This parameter indicates the maximum value set at heating, in correspondence with
the minimum outdoor air temperature (user menu index (b) This parameter is visible
only if the compensation function is activated (use menu index (5)).
(*)
(*):
- the maximum limit can be configured via the parameter (t) of the installer menu;
- if the parameter (8) of the installer menu is set at 4, the maximum limit becomes
70°C in order to allow insertion of a set-point for boiler adjustment;

Setting the outside air temperature 1 (heating)

MAX
value
This parameter indicates the minimum outside air temperature taken into consideration for heating
50 °C
compensation. This parameter is only visible if the compensation function has been activated (index (5)
user menu).
Parameter function
Parameter function
Parameter function
Parameter function
Parameter function
Parameter function
Parameter visible ONLY on units with condensation control
device on board
Parameter ONLY visible on units fitted with twin compressor
Parameter ONLY visible on units fitted with inverter com-
pressor
IMDCFJ. 12.05 6343841_03
55
EN