INSTALLATION
5.1 Safety instructions
DANGER!
Risk of injury from high pressure in the equipment!
▶ Before loosening the lines and valves, turn off the pressure and
vent the lines.
Risk of injury due to electrical shock!
▶ Before reaching into the system, switch off the power supply and
secure to prevent reactivation!
▶ Observe applicable accident prevention and safety regulations for
electrical equipment!
WARNING!
Risk of injury from improper installation!
▶ Installation may be carried out by authorized technicians only and
with the appropriate tools!
Risk of injury from unintentional activation of the system and an
uncontrolled restart!
▶ Secure system from unintentional activation.
▶ Following installation, ensure a controlled restart.
WARNING!
Danger – escaping medium!
Leaking connections if seals not seated properly, if manifold uneven or if
surface quality of the manifold inadequate.
▶ Make certain the seals included with delivery are properly seated in
the valve.
▶ Ensure that the manifold is even.
▶ Ensure that the surface quality of the manifold is adequate.
Insert the seal into the body.
Screw the body onto the manifold (max. 1.5 Nm).
Attach the coil and screw on the nut (max. 5 Nm).
Verschlussplatte
8
Control of pulse version
Correct polarity is essential to ensure that the device func-
tions: Note identification on the upper side of the coil.
Pulse duration at least 50 ms.
Protective conductor connection
Terminal 2
Terminal 1
Polarity
Specifications
Valve (P seat)
- Switch ON +
will be opened
Valve (P seat)
+ Switch OFF -
will be closed
Use only cable plug without electrical wiring for pulse versions.
Mutter
Spule
Dichtung
Anschlussplatte
english
Terminal connections
(+) on terminal 2,
(–) on terminal 1
(+) on terminal 1,
(–) on terminal 2
5.2 Fluid installation
Installation position: any, actuator preferably upwards.
Procedure:
Clean any possible dirt off the pipelines and flange connections.
Install a dirt trap to prevent malfunctions (0.2 ... 0.4 mm).
Pay attention to the flow direction of the valve: from 1 (P) →
2(A) (CFA) or from 1(P) → 2(B) (CFB).
Valve with threaded connection:
Use PTFE tape as sealing material.
NOTE!
Caution risk of breakage!
• Do not use the coil as a lifting arm.
Hold the device with a Open-end wrench on the body and screw
into the pipeline.
Valve with flanged connection:
Remove the cover plate.
Loosen the nut on the coil and remove coil.
english
5.3 Electric installation
WARNING
Risk of injury due to electrical shock!
▶ Before reaching into the system, switch off the power supply and
secure to prevent reactivation!
▶ Observe applicable accident prevention and safety regulations for
electrical equipment!
If the protective conductor contact between the coil and body is
missing, there is danger of electrical shock!
▶ Always connect protective conductor.
▶ Check electrical continuity between coil and body.
Note the voltage and current type as specified on the type label.
Procedure:
Check that the seal is correctly seated.
Screw cable plug tightly onto coil (max. 1 Nm).
5.4 Rotation of coil
WARNING!
Electric shock!
If the protective conductor contact between the coil and body is
missing, there is danger of electrical shock!
▶ Check protective conductor contact after installing the coil.
Overheating, Risk of fire!
Connection of the coil without pre-assembled valve will result in
overheating and destroy the coil.
▶ Connect the coil with assembled valve only.
The coil can be turned by 4 x 90° (for
Nut
max. 5 Nm
block installation only 2 x 180°).
Procedure:
O-ring
Fitting
english
Loosen nut.
Turn coil.
Tighten nut with a open-end wrench
(max. 5 Nm).