9. DC connection

This chapter explains the requirements and process for wiring the DC wiring to the unit.
Read carefully before starting the connection process.
INFO
Consult section "Important safety instructions" and the following instructions before working on the unit.

9.1. Safety instructions for the DC connection

DANGER
Make sure there is no voltage present on the unit before starting the connection.
Do not switch on the power to the unit until you have successfully made the rest of the connections and the unit
is closed.
Use the Personal Protective Equipment specified in section "Personal Protective Equipment (PPE)".
While connecting the inverter, make sure of the proper installation of the cables on the unit´s terminals so that
parts of accessible wires do not remain live.
When the PV array is exposed to sunlight the inverter has DC voltage.
CAUTION
Ingeteam accepts no liability for any damages caused by an incorrect connection.
INFO
The wiring must be routed inside the unit via a conduit, which is inserted through a coupling in order to
maintain the unit's protection class.

9.2. Wiring requirements for the DC connection

CAUTION
The type of cabling for the connection must have dimensions in line with current regulations in the country of
installation and according to the type of installation and maximum current and voltage of the PV array.

9.2.1. STD Version

The maximum current allowed per unit is 168 Adc. The admissible section for the DC cables is 70 mm
300 mm
, with cable diameters between 12 and 35 mm. The cables must finish in an M12 spade terminal. The
2
maximum width of the spade must not exceed 40 mm.
The cable conductor material may be copper or aluminum. If the connection of aluminum cables is required, the
installer must provide the necessary means to prevent galvanic coupling (bipolar terminals, bimetallic interfaces,
etc.).

9.2.2. PRO Version

This version accepts up to 20 strings. The unit includes the aerial photovoltaic connectors required for connecting
each string to the unit. The photovoltaic connectors used are Phoenix contact Sunclix PV-C4F-S 2.5-6 (+) and
PV-C4M-S 2.5-6 (-). To perform the connection between the string cables and their corresponding connectors, see
the manufacturer documentation.
The accepted section for the aerial connectors is 2.5 mm
88
to 6 mm
.
2
2
ABZ2011IQM01_C- Installation and Operation Manual
DC connection
to
2