Ingeteam
Connection of accessories
In the case of the RES input, a resistance of 15 kOhms allows the unit to connect, and a higher or lower resistance
stops the inverter and prevents it from restarting.
7.5.1. Cabling requirements
The digital input connectors admit a section of 0.25 mm
to 2.5 mm
2
2
7.5.2. Connection process
To insert the cable into the unit, use one of the precut holes protected with a cap. Remove the cap and fit the
corresponding M16 packing gland. A multi-pole hose must be used for all the digital inputs to be used.
84
ABZ2011IQM01_C- Installation and Operation Manual