DC connection
There are several restrictions regarding the dimensioning of the strings connected to the unit:
•
Each individual string must not exceed 13 Adc.
•
The sum of the currents of all the string must in no case exceed 168 Adc.
CAUTION
The strings connected to the unit's connectors must be electrically independent of each other. That is, there
must not be any strings with a current higher than that permitted separated into several connectors, as the
current distribution is never guaranteed.
The cabling used for the connection must have dimensions in line with current regulations in the country of
installation and according to the type of installation, connectors, and maximum current and voltage of the PV array.
9.3. DC connection process
9.3.1. STD Version
With the switch OFF and the AC cables without voltage, open the unit's lower compartment.
1.
Uninstall the polycarbonate guard.
2.
Follow the steps below according to the cable diameter.
Option 1. Cable diameter 12 ~ 20 mm: cables pass through M40 packing gland
a.
Ensure that the spade terminal dimensions allow it to pass through the M40 packing gland.
b.
Fit the spade terminal on the cable.
c.
Loosen the head of the M40 packing gland and remove the cap.
d.
Pass the power cables through the M40 packing gland, using the diameter reducer provided.
e.
Place each terminal in its terminal block, respecting the polarity, and tighten the packing gland head to
ensure the sealing.
Option 2. Cable diameter 20 ~ 28 mm: cables pass through M40 cable grommet membrane
a.
Remove the M40 packing gland.
b.
Install the cable grommet membrane in the hole.
c.
Fit the spade terminal on the cable.
d.
Pass the cables through the M40 membrane (a soapy solution can be used).
e.
Place each terminal in its terminal block respecting the polarity.
Option 3. Cable diameter 28 ~ 35 mm: cables pass through M50 cable grommet membrane
a.
Remove the M50 caps.
b.
Install the cable grommet membrane in the hole.
c.
Fit the spade terminal on the cable.
d.
Pass the cables through the M50 membrane (a soapy solution can be used).
ABZ2011IQM01_C - Installation and Operation Manual