Maintenance; Safety Conditions; Condition Of The Housing; Condition Of Cables And Terminals - Ingeteam INGECON SUN 160TL Manuel D'installation

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 163

Maintenance

14. Maintenance
The recommended maintenance tasks must be carried out at least annually, except where otherwise stated.

14.1. Safety conditions

DANGER
All the maintenance checks included here must be carried out with the machine stopped, under safe conditions
for handling, including those specified by the client for these types of operation.
An open housing never implies an absence of voltage in the unit, so only qualified personnel may access the
unit, following the safe operation guidelines stipulated in this document.
Before opening the unit, you must remove the power (see section "13. Shutting down the unit").
Make sure there is no voltage present on the unit before starting maintenance operations.
While connecting the inverter, make sure of the proper installation of the cables on the unit´s terminals so that
parts of accessible wires do not remain live.
When carrying out maintenance work on the unit, you must wear the personal protective equipment specified in
section "Personal Protective Equipment (PPE)" of this document.
CAUTION
You must consider the set of conditions listed below as minimum requirements.
Ingeteam accepts no liability for any damages caused by improper use of the equipment. You must propose
in advance to Ingeteam any work carried out on any equipment which implies a modification of the original
electrical arrangements. These must be studied and approved by Ingeteam.
After completing the maintenance task, replace the front cover and secure it with the bolts supplied.
INFO
The wiring must be routed inside the unit via a conduit, which is inserted through a coupling in order to
maintain the unit's protection class.

14.2. Condition of the housing

A periodic visual check of the condition of the housing must be carried out, confirming the condition of the seals
and the cover, as well as the fixing of the units to their anchor points on the wall. In addition, you must check the
condition of the housing and the absence of dents or scratches that might degrade the housing or cause it to lose
its protection classification. If these types of defect are noticed, the affected parts must be repaired or replaced.
Check the correct fixing of the housing components to their corresponding anchoring points.
Check the condition of the door seal in the unit's lower compartment.

14.3. Condition of cables and terminals

You must perform an annual inspection of the cable and terminals conditions:
Check the correct path of the cables so they do not come into contact with live parts.
Check the insulation deficiencies and hot spots by checking the color of the insulation and terminals.
Check that the connections have the correct tightening torque.
ABZ2011IQM01_C - Installation and Operation Manual
Ingeteam
DE
EN
ES
FR
IT
PT
103

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Ingecon sun 3 play160tlIngecon sun sérieIngecon sun 3play 100tl stdIngecon sun 3play 100tl pro

Table des Matières