Control Connection X26; Terminal Assignment - Lenze ECS K001 Série Instructions De Montage

Module condensateur en montage sur panneau
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

4.3

Control connection X26

Terminal assignment

Terminal
X26
The charging current limitation is bridged if X26 = HIGH (24 V DC).
ƒ
The polarity does not influence the function of the charging current
ƒ
limitation.
Cable cross−sections and screw−tightening torques
Cable type
Flexible
For control cables, we recommend a cable cross−section of 0.25 mm
EDKCSEK002 DE/EN/FR 3.0
Function
Connection for bridging the charging current
limitation
Wire end ferrule
Without wire end ferrule
l
Electrical installation
Control connection X26
Electrical data
21.8 ... 30 V DC,
max. 1.5 A
Possible cable
Tightening torque
cross−sections
2
0.2 ... 2.5 mm
0.5 ... 0.8 Nm
(AWG 24 ... 12)
(4.4 ... 7.1 lb−in)
4
Stripping
length
5 mm
2
!
53

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Ecs k002 sérieEcsek001Ecsek002

Table des Matières