Electrical installation

6.1

Important notes

(
Stop!
Possible overheating of the brake resistor during operation
Inadequate heat dissipation during operation can cause the brake
resistor to overheat.
Possible consequences:
ƒ
ƒ
Protective measures:
ƒ
ƒ
6.2

Connection data

Connection
RB1, RB2
(brake resistor)
PE (protective
conductor)
T1, T2
(thermal
contact)
EDKRBD180R DE/EN/FR 9.0
The brake resistor is destroyed.
The drive is not braked but coasts to a standstill.
Always connect the thermal contact of the brake resistor.
Integrate the thermal contact into the overall equipment
monitoring apparatus in such a way that the supply of power to
the standard device is switched off if the brake resistor overheats
(e.g. switch−off by means of mains contactor control).
Cable gland
M25
M12
l
Electrical installation
Important notes
Type of
Size of connection Tightening torque
connection
0.5 ... 10 mm
Screw terminal
20 ... 6 AWG
Screw
0.25 ... 4 mm
Screw terminal
24 ... 12 AWG
2
1.5 ... 1.8 Nm
13.3 ... 15.9 lb−in
3.0 ... 3.7 Nm
M5
26.6 ... 32.7 lb−in
2
0.6 ... 0.8 Nm
5.3 ... 7.1 lb−in