Mechanical installation

Important notes

3
Mechanical installation
3.1
Important notes
Capacitor modules of the ECS series feature enclosure IP20 and therefore
ƒ
are intended for installation in control cabinets.
If the cooling air contains pollutants (dust, fluff, grease, aggressive gases):
ƒ
Take suitable preventive measures, e.g. separate air duct, installation of
filters, regular cleaning.
Possible mounting positions:
ƒ
Vertically at the mounting plate
DC bus connections (X23) at the top
Connection for short−circuiting of the charging current limitation (X26)
at the bottom
Maintain the specified clearances (above and below) to other
ƒ
installations!
If the ECSZS000X0B shield mounting kit is used, an additional clearance
is required.
Ensure unimpeded ventilation of cooling air and outlet of exhaust air.
Several modules of the ECS series can be installed in the control cabinet
next to each other without any clearance.
The mounting plate of the control cabinet must be electrically conductive.
ƒ
In the case of continuous vibrations or shocks use shock absorbers.
ƒ