Technical data
General data and operating conditions
General electrical data
EMC
Noise emission
Noise immunity
Insulation resistance
Enclosure
Protective insulation of control circuits
1)
42
Compliance with requirements in accordance with EN 61800−3
Compliance with limit value class A in accordance with EN 55011
(achieved by using collective filters typical for the application)
Requirements in accordance with EN 61800−3
Requirement
1)
ESD
Conducted high
frequency
RF interference (housing) EN 61000−4−3
Burst
Surge (surge voltage on
mains cable)
Overvoltage category III in accordance with VDE 0110
IP 20 (NEMA 250 type1) for
l
Standard mounting (built−in unit)
Mounting in cold−plate technique
l
Mounting with thermal separation (push−through technique),
l
IP54 on heatsink side
Protective separation from the mains
Double/reinforced insulation in accordance with EN 61800−5−1
Rated insulation voltage 300 V x 2
Noise immunity in the above−mentioned severities must be guaranteed through the
control cabinet! The user must check the compliance with the severities!
Standard
EN 61000−4−2
EN 61000−4−6
EN 61000−4−4
EN 61000−4−5
l
Severities
3, i. e.
l
8 kV with air
discharge
6 kV with contact
l
discharge
10 V; 0.15 ... 80 MHz
3, i. e. 10 V/m;
80 ... 1000 MHz
3/4, i. e. 2 kV/5 kHz
3, e. i. 1.2/50 ms
1 kV phase/phase
l
l
2 kV phase/PE
EDKCSEK002 DE/EN/FR 3.0