Cable cross−sections and screw−tightening torques
Cable type
Terminal strip X23
rigid
flexible
Shielded cables
The following factors decisively determine the effect of the shielded cables:
Good shield connection
ƒ
Ensure a contact surface as large as possible
Low shield resistance
ƒ
Only use shields with tin−plated or nickel−plated copper braids (shields
with steel braids cannot be used).
High overlap rate of the braid
ƒ
At least 70 ... 80 % with 90° overlap angle
The ECSZS000X0B shield mounting kit includes a wire clamp and shield sheet.
EDKCSEK002 DE/EN/FR 3.0
Wire end ferrule
without wire end ferrule
with wire end ferrule
with TWIN wire end
ferrule
l
Electrical installation
Power terminals
Possible cable
Tightening torque
cross−sections
2
0.2 ... 10 mm
(AWG 24 ... 8)
2
0.2 ... 10 mm
(AWG 24 ... 8)
1.2 ... 1.5 Nm
2
(10.6 ... 13.3 lb−in)
0.25 ... 6 mm
(AWG 22 ... 10)
2
0.25 ... 4 mm
(AWG 22 ... 12)
4
Stripping
length
5 mm
51