Type 2030, 2031, 2031 K, 2032,
2033, 2037
8.
INSTALLATION
8.1. Safety instructions
DANGER!
Risk of injury from high pressure in the equipment!
• Before loosening the lines and valves, turn off the pressure and
vent the lines.
Risk of injury due to electrical shock!
• Before reaching into the device or the equipment , switch off the
power supply and secure to prevent reactivation!
• Observe applicable accident prevention and safety regulations
for electrical equipment!
WARNING!
Risk of injury from improper installation!
• Installation may be carried out by authorized technicians only
and with the appropriate tools!
Risk of injury from unintentional activation of the system and
an uncontrolled restart!
• Secure system from unintentional activation.
• Following assembly, ensure a controlled restart.
8.2. Before installation
• Before connecting the valve, ensure the pipelines are flush.
• The flow direction is optional.
Installation
8.2.1. I nstallation position 2/2-way valve
• The piston-controlled diaphragm valve can be installed in any
installation position, preferably with the actuator face up.
Installation for self-drainage of the housing
It is the responsibility of the installer and operator to ensure
self-drainage.
To ensure self-drainage:
→
Install housing inclined by angle α = 10° bis 40° to the horizontal
(see Fig. 12).
→
Observe an inclination angle of 1° – 5°. Forged and cast
housings feature a mark which must face upwards
(12 o'clock position, see Fig. 13).
→
The bore (in the actuator base) for monitoring leaks must be at
the lowest point.
Fig. 12:
Installation position for self-drainage of the housing
english
Angle α: 10° to 40°
Inclination to the
line axis 1° ... 5°
15