Mounting The Cm-Rc-01 Basic Kit; Mounting The Cable Holders - Bitzer CM-RC-01 Instructions De Montage

Masquer les pouces Voir aussi pour CM-RC-01:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

When working on the electrical and/or electronic
system, please observe the following
WARNING
Risk of electric shock!
Before working on the terminal box, module
housing and electrical lines: Switch off the main
switch and secure it against being switched on
again!
Close the terminal box and the module housing
before switching on again!
NOTICE
!
!
The compressor module may be damaged or
fail!
Never apply any voltage to the terminals of CN7
to CN12 – not even for test purposes!
The voltage applied to the terminals of CN13
must not exceed 10 V!
The voltage applied to terminal 3 of CN14 must
not exceed 24 V! Do no apply voltage to the
other terminals!
4
Never apply voltage to the voltage outputs, not even for
testing.

3 Mounting the CM-RC-01 basic kit

Procedure to follow for mounting the CM-RC-01 basic
kit of the compressor module add-on kit:

• Mounting the cable holders.

• Removing the SE-B* protection device.
• Connecting the oil heater.
• Mounting the discharge gas temperature sensor.
• Mounting the oil monitoring.
• Laying the cables and closing the cable ties.
• Closing the cover, screwing the compressor module
to the terminal box.
3.1 Mounting the cable holders
Mount 2 cable holders each to the cylinder
heads (see figure).
• To this end, loosen the corresponding screws
on the cylinder head, insert the screws again
with cable holders and tighten them (tighten-
ing torque 80 Nm).
• Attach plastic clip on the outer fixtures and in-
sert cable ties.
KW-232-1