3.3 Connecting the oil heater

3.4 Mounting the discharge gas temperature sensor

After mounting new components such as discharge gas
temperature sensor, pressure transmitter, injection
nozzle or injection valve:
6
• Properly position the compressor module on
the terminal box. The long side that is
provided with the numerous cable bushings of
the compressor module must point in the dir-
ection of the suction gas valve.
• Screw the protective earth conductor onto the
module housing.
• Put the oil heater cable through a screwed
cable gland on the compressor module and
connect it to the CN4 terminal strip.
• Guide the oil heater cable to the compressor
module as shown in the figure.
Information
For oil heater mounting, see Technical
Information KT-150.
WARNING
Serious injuries are possible. New component
may suddenly become detached.
Check the thread.
Carefully screw in the new component. Observe
the tightening torques!
Perform a tightness test before commissioning!