If no additional extension kits are mounted:
• Proceed with the other electrical connections on the
CM-RC-01 (see chapter Further electrical connec-
tions on the CM-RC-01, page 8).
• Screw the protective earth conductor onto the ter-
minal box cover and attach the cover to the module
housing (see chapter Screwing the cover onto the
module housing, page 8).
• Lay the cables and close the cable ties (see chapter
Laying the cables, page 9).
KW-232-1
• Press the solenoid coil onto the armature until
it engages.
NOTICE
!
!
Risk of compressor damage!
Use only suitable original solenoid coils!
• Insert the electric connector of the device and
screw it down (tightening torque 5 Nm).
• Shorten the cables as needed, pass them
through the cable glands on the compressor
module into the module housing and connect
them to the CN6 terminal strip.
4.2 Mounting the "Pressure transmitter" extension kit
NOTICE
!
!
The two pressure transmitters must not be inter-
changed. They differ by the component number
engraved in the component:
High pressure transmitter: 2CP5-71-47.
Low pressure transmitter: 2CP5-71-49.
Information
Alternative mounting position for discharge gas
temperatures exceeding 135°C:
Connect the pressure transmitters to the dis-
charge gas line, as close as possible to the
valves using one refrigerant hose each. Length
of the refrigerant hose: at least 200 mm to avoid
overheating of the transmitter.
11