KW-233-2 Anleitung zur Montage des CM-RC-01 Komplettierungsbausatzes Originaldokument Deutsch ..............................Instructions for mounting the CM-RC-01 add-on kit Translation of the original document English..............................Instructions de montage du kit complémentaire CM-RC-01 Traduction du document original Français..............................4FES-3(Y) .. 4BES-9(Y)
Page 2
3.10 Weitere elektrische Anschlüsse am CM-RC-01..................... 8 3.11 Modulgehäuse schließen.......................... 8 3.12 Kabelhalter montieren und Kabel verlegen.................... 9 4 Montage der optionalen CM-RC-01 Erweiterungsbausätze ................ 9 4.1 Erweiterungsbausatz "Leistungsregelung" (CRII) und "Anlaufentlastung" (SU) montieren...... 10 4.2 Erweiterungsbausatz "Druckmessumformer" montieren ................ 11 4.3 Erweiterungsbausatz "Zusatzventilator" montieren .................. 12 5 Kommunikation über die BEST SOFTWARE aufbauen .................
Page 3
1 Einleitung hen. Jede Person, die daran arbeitet, muss deshalb dieses Dokument sorgfältig lesen! Es gelten zwingend Dieses Dokument beschreibt die Montage des CM-RC-01-Verdichtermodul Komplettierungsbausatzes • die einschlägigen Sicherheitsvorschriften und Nor- an die Verdichter 4FES-3(Y) .. 4BES-9(Y). Beschrieben men, wird der nachträgliche Anbau aller Bauteile des Basis- •...
Page 4
An die Klemmen von CN7 bis CN12 keine Spannung anlegen – auch nicht zum Prüfen! An die Klemmen von CN13 maximal 10 V anle- Abb. 1: Übersicht aller Bauteile des CM-RC-01 Basis-Bausatzes für gen! An die Klemme 3 von CN14 maximal 24 V, an die Verdichter 4FES-3(Y) ..
Page 5
▶ Anschließend den Anschlusskasten des Verdichters 3.3 Anschlusskasten vom Verdichter auf die Halterung stellen und alles mit den 5 abschrauben Schrauben im Anschlusskasten an den Verdichter schrauben. ▶ Die 5 markierten Befestigungsschrauben im An- schlusskasten des Verdichters lösen und den An- schlusskasten vom Verdichter abnehmen.
Page 6
▶ Anschlusskasten schließen und Deckel festschrau- ben. 3.7 Ölheizung anschließen ▶ Kabel der Ölheizung durch eine Kabelverschrau- bung am Verdichtermodul führen und an Klemmleis- te CN4 anschließen. Information Montage der Ölheizung, siehe Technische In- formation KT-150. 3.6 Verdichtermodul auf die Halterung schrauben ▶...
Page 7
3.8 Druckgastemperaturfühler montieren Nach Montage neuer Bauteile wie z. B. Druckgastem- peraturfühler, Druckmessumformer, Einspritzdüse oder Einspritzventil: WARNUNG Schwere Verletzungen möglich. Neues Bauteil kann sich schlagartig lösen. Gewinde prüfen. Neues Bauteil sorgfältig einschrauben. Anzugs- momente beachten! Vor Inbetriebnahme Dichtheitsprüfung durchfüh- ren! ▶...
Page 8
Anschlussbohrung abfließen kann. CM-RC-01 Erweiterungsbausätze, Seite 9). Schraube (M20x1,5) am Lagerdeckel ausschrauben und Gewindeloch sorgfältig reinigen. 3.10 Weitere elektrische Anschlüsse am CM-RC-01 Glaskegel der Prismaeinheit innen und außen auf • Spannungsversorgung des Verdichtermoduls an Sauberkeit prüfen und ggf. reinigen. Klemmleiste CN1 (115 .. 230 V +10%/-15%, 50/60 Hz)
Page 9
3.12 Kabelhalter montieren und Kabel verlegen 4 Montage der optionalen CM-RC-01 Erweiterungsbausätze ▶ Je einen Kabelhalter an den Zylinderköpfen außen Die Montage der optionalen Erweiterungsbausätze des montieren (siehe roter Kreis). Verdichtermodul-Komplettierungsbausatzes enthält fol- ▶ Dazu die entsprechenden Schrauben am Zylinder- gende Bauteile und Arbeitsschritte: kopf lösen, die Schrauben mit Kabelhaltern wieder...
Page 10
Schrauben abwechselnd anziehen (Anzugsmoment 80 Nm). Falls keine weiteren Erweiterungsbausätze montiert werden: • Weitere elektrische Anschlüsse am CM-RC-01 vor- nehmen (siehe Kapitel Weitere elektrische Anschlüs- se am CM-RC-01, Seite 8). ▶ Magnetspule auf den Anker aufdrücken bis sie ein- rastet.
Page 11
4.2 Erweiterungsbausatz "Druckmessumformer" ▶ Kabel des Niederdruckmessumformers an Klemm- montieren leiste CN12, Klemmen 4, 5, 6 (Bezeichnung psuc) am Verdichtermodul anschließen. HINWEIS ▶ Anschluss der Kabel beachten! Die beiden Druckmessumformer dürfen nicht vertauscht werden. Sie unterscheiden sich durch die Beschriftung "HP" oder "LP" auf dem Bauteil: Hochdruckmessumformer: HP.
Page 12
Falls keine weiteren Erweiterungsbausätze montiert werden: • Weitere elektrische Anschlüsse am CM-RC-01 vor- nehmen (siehe Kapitel Weitere elektrische Anschlüs- se am CM-RC-01, Seite 8). • Kabelhalter montieren, Kabel verlegen, Kabelbinder schließen (siehe Kapitel Kabelhalter montieren und Kabel verlegen, Seite 9).
Page 13
▶ Bluetooth Passwort eingeben. Werkseinstellung ab Firmwareversion 2.6.58.00: "8670", vorige Versio- nen: "2". ➙ Das Verdichtermodul ist jetzt mit dem PC oder dem mobilen Endgerät verbunden. Abb. 2: CM-RC-01 mit der BEST SOFTWARE verbinden 5.1 Konfiguration mit der BEST SOFTWARE ▶ Schaltfläche anklicken (4). VERBINDEN Information ➙...
Page 14
• Zusatzventilator. • CRII Leistungsregelung mit Anzahl der montierten Leistungsregler. • Einsatzgrenzüberwachung. • Nieder- und Hochdruckschalter. Anschließend diese Benutzeinstellung zum Gerät über- tragen. Abb. 4: Benutzereinstellungen zum Verdichtermodul übertragen KW-233-2...
Page 15
2.3 Residual risks .............................. 16 2.4 Safety references............................ 16 2.4.1 General safety references........................ 16 3 Mounting the CM-RC-01 basic kit ........................ 17 3.1 Opening the cable bushing on the terminal box .................. 17 3.2 Removing the SE-B* motor protection device ..................... 17 3.3 Unscrewing the terminal box from the compressor .................. 18 3.4 Mounting the fixture of the compressor module................... 18...
Page 16
2.3 Residual risks This document describes the procedure to follow for Compressors, electronic accessories and further sys- mounting the CM-RC-01 compressor module add-on kit tem components may present unavoidable residual to the compressor models 4FES-3(Y) .. 4BES-9(Y). risks. Therefore, any person working on it must care-...
Page 17
Never apply any voltage to the terminals of CN7 to CN12 – not even for test purposes! Fig. 1: Overview of all components of the CM-RC-01 basic kit for the The voltage applied to the terminals of CN13 must not exceed 10 V! compressors 4FES-3(Y) ..
Page 18
▶ Then put the compressor terminal box onto the fix- 3.3 Unscrewing the terminal box from the ture and fasten everything to the compressor using compressor the 5 screws in the terminal box. ▶ Loosen the 5 marked fixing screws in the com- pressor terminal box and remove the terminal box from the compressor.
Page 19
▶ Close the terminal box and screw down the cover. 3.7 Connecting the oil heater ▶ Put the oil heater cable through a screwed cable gland on the compressor module and connect it to the CN4 terminal strip. Information For oil heater mounting, see Technical Informa- tion KT-150.
Page 20
3.8 Mounting the discharge gas temperature If subsequently mounting the prism unit of the oil monit- sensor oring: After mounting new components such as discharge gas NOTICE temperature sensor, pressure transmitter, injection Risk of refrigerant loss! nozzle or injection valve: Check the thread.
Page 21
Following this, any optional extension kits can be 3.12 Mounting the cable holders and laying the mounted (see chapter Mounting the optional CM-RC-01 cables extension kits, page 22). ▶ Mount one cable holder each on the outside of the 3.10 Further electrical connections on the CM- cylinder head (see red circle).
Page 22
KT-101 and KT-110. ▶ Remove the oval flange and seal from the CRII/SU cylinder head and clean the sealing surface. 4 Mounting the optional CM-RC-01 extension kits ▶ Apply a new seal, paying attention to the guide pin positions! Required components and procedure to follow for mounting the optional extension kits of the compressor ▶...
Page 23
If no additional extension kits are mounted: • Proceed with the other electrical connections on the CM-RC-01 (see chapter Further electrical connec- tions on the CM-RC-01, page 21). • Mount the cable holders, lay the cables and close the cable ties (see chapter Mounting the cable hold- ers and laying the cables, page 21).
Page 24
If no additional extension kits are mounted: • Proceed with the other electrical connections on the CM-RC-01 (see chapter Further electrical connec- tions on the CM-RC-01, page 21). • Mount the cable holders, lay the cables and close the cable ties (see chapter Mounting the cable hold- ers and laying the cables, page 21).
Page 25
• Proceed with the other electrical connections on the ➙ The following appears for selection: BEST CONVERTER CM-RC-01 (see chapter Further electrical connec- or B LUETOOTH tions on the CM-RC-01, page 21). ▶ SelectionBEST CONVERTER • Mount the cable holders, lay the cables and close Click on the C button.
Page 26
Configuration via BEST SOFTWARE (see figure 4, page 26) At least the following parameters need to be set / selec- ted in the C menu: ONFIGURATION • Compressor type. • Refrigerants. • Motor starter function. • Serial number of the compressor. Depending on the equipment installed, the following parameters may have to be enabled: •...
Page 27
2.4 Indications de sécurité .......................... 28 2.4.1 Indications de sécurité générales .................... 28 3 Montage du kit de montage de base CM-RC-01 ..................... 29 3.1 Ouvrir le passage de câble sur la boîte de raccordement ................ 29 3.2 Démonter le dispositif de protection SE-B*.................... 29 3.3 Dévisser la boîte de raccordement ...................... 30...
Page 28
2.3 Risques résiduels Ce document décrit le montage du kit complémentaire Des risques résiduels inévitables sont susceptibles pour le module du compresseur CM-RC-01 sur les d'être causés par les compresseurs, les accessoires compresseurs 4FES-3(Y) .. 4BES-9(Y). Il décrit la pro- électroniques et d'autres composants de l'installation.
Page 29
M16 de droite. ▶ Retirer ensuite le couvercle de la boîte de raccorde- 3 Montage du kit de montage de base CM-RC-01 ment. Procédure à suivre pour monter le kit de montage de base CM-RC-01 du kit complémentaire pour le module...
Page 30
▶ Poser ensuite la boîte de raccordement du com- 3.3 Dévisser la boîte de raccordement presseur sur le support de fixation et visser l’en- semble sur le compresseur avec les 5 vis dans la ▶ Desserrer les 5 vis de fixation marquées dans la boîte de raccordement.
Page 31
▶ Fermer la boîte de raccordement et visser le cou- vercle. 3.7 Raccorder le réchauffeur d'huile ▶ Faire passer les câbles du réchauffeur d'huile à tra- vers un passe-câble à vis du module du compres- seur et les raccorder au bornier CN4. Information Pour le montage du réchauffeur d’huile, voir l’Information Technique KT-150.
Page 32
3.8 Monter la sonde de température du gaz de Information refoulement Livraison en état prêt au rééquipement : Si l'unité prisme du contrôle d'huile a été com- Après le montage de nouveaux composants tels que la mandée préassemblée, l'ensemble du compres- sonde de température du gaz de refoulement, le trans- seur aura déjà...
Page 33
Vous pouvez monter ensuite les kits d’extension op- tionnels (voir chapitre Montage des kits d’extension op- tionnels du CM-RC-01, page 34). 3.10 Autres connexions électriques sur le CM- RC-01 • Alimentation en tension du module du compresseur au bornier CN1 (115 ..
Page 34
4.1 Monter les kits d’extension « Régulation de puissance » (CRII) et « Démarrage à vide » (SU) Information Pour permettre le montage des vannes magné- tiques pour la régulation de puissance (CRII) et le démarrage à vide (SU), les têtes de culasses correspondantes CRII et SU doivent déjà être préassemblées sur le compresseur.
Page 35
Si aucun autre kit d’extension doit être monté : • Effectuer les autres connexions électriques sur le CM-RC-01 (voir chapitre Autres connexions élec- triques sur le CM-RC-01, page 33). • Monter les porte-câbles, poser les câbles et fermer les courroies de câble (voir chapitre Monter le porte-...
Page 36
écrous joints (voir petite figure). Si aucun autre kit d’extension doit être monté : • Effectuer les autres connexions électriques sur le CM-RC-01 (voir chapitre Autres connexions élec- triques sur le CM-RC-01, page 33). • Monter les porte-câbles, poser les câbles et fermer les courroies de câble (voir chapitre Monter le porte-...
Page 37
• Effectuer les autres connexions électriques sur le ➙ L'écran suivant apparaît pour la sélection : C ONVER CM-RC-01 (voir chapitre Autres connexions élec- BESTou B TISSEUR LUETOOTH triques sur le CM-RC-01, page 33). ▶ Sélection C BEST : ONVERTISSEUR • Monter les porte-câbles, poser les câbles et fermer...
Page 38
5.1 Configuration avec BEST SOFTWARE Information Pour de plus amples informations sur la sur- veillance des paramètres de fonctionnement, le raccordement électrique et la communication avec BEST SOFTWARE, voir Information Tech- nique KT-230. Configuration avec BEST SOFTWARE (voir figure 4, page 38) Régler / sélectionner au moins les paramètres suivants dans le menu C...
Page 39
80522502 // 10.2020 Änderungen vorbehalten Subject to change Toutes modifications réservées BITZER Kühlmaschinenbau GmbH Peter-Schaufler-Platz 1 // 71065 Sindelfingen // Germany Tel +49 7031 932-0 // Fax +49 7031 932-147 bitzer@bitzer.de // www.bitzer.de Änderungen vorbehalten // Änderungen vorbehalten // Subject to change // Toutes modifications réservées80522502 // 10.2020...