6
4 Technical data
Input data
Measuring ranges in bar
Overload pressures in bar
1)
Burst pressures
Mechanical connection
Pressure transfer fluid
Torque rating
E
Parts in contact with fluid
Output data
Output signal,
permitted load resistance
Accuracy to DIN 16086,
Max. setting
Accuracy at min.setting
(B.F.S.L)
Temperature compensation
Zero point
Temperature compensation
Over range
Non-linearity at
max. setting
to DIN 16086
Hysteresis
Repeatability
Rise time
Long term drift
Environmental Conditions
Compensated temperature range
Operating temperature range
Storage temperature range
Fluid temperature range
- mark
5)
-mark
Vibration resistance according
to DIN EN 60068-2-6
at 10 .. 500 Hz
Protection class to
DIN EN 60529
6)
Other data
Supply voltage
for use acc. to UL spec.
Residual ripple of supply
voltage
Current consumption
3 conductor
Service life
Weight
1)
G1/2 and G1/4 with additional front O-ring seal max. 1500 bar
2)
Other seal materials available on request
3)
For G1/2 and G1/4 with additional front O-ring seal -10 .. +85 °C
4)
-25°C with FKM seal, -30°C on request
5)
Environmental conditions according to 1.4.2 UL 61010-1; C22.2 No. 61010-1
6)
with mounted mating connector in corresponding protection classt
Status 2021-02-10
-1..1 -1..9 2.5
3
32
8
in bar
5
48
12
G1/2A ISO 1179-2
G1/2 with additional front O-ring seal
G1/2 with additional front O-ring seal and cooling zone
G1/4 with additional front O-ring seal
G1/4A ISO 1179-2
Silicon-free oil
45 Nm (G1/2)
20 Nm (G1/4)
2)
Mech. connection: Stainless steel (measuring cell stainless steel
Seal: FKM
O-Ring: FKM
4 .. 20 mA, 2 conductors
0 .. 10 V, 3 conductor
HDA 4400
≤ ± 0.5 % FS typ.
≤ ± 1,0 % FS max
≤ ± 0.25 % FS typ.
≤ ± 0.5 % FS max.
≤ ± 0.015 % FS / °C typ.
≤ ± 0.025 % FS / °C max.
≤ ± 0.015 % FS / °C typ.
≤ ± 0.025 % FS / °C max.
≤ ± 0.3 % FS max.
≤ ± 0.4 % FS max.
≤ ± 0.1 % FS max.
≤ 1 ms
≤ ± 0.3 % FS / year typ.
-25 .. +85 °C
3)4)
-25 .. +85 °C
-40 .. +100 °C
4)
30 .. +100 °C / -25 .. +100 °C
30 .. +150 °C / -25 .. +150 °C at G1/2 with additional front O-ring seal and cooling zone
EN 61000-6-1 / 2 / 3 / 4
certificat-Nr.: E318391
≤ 20 g
IP 65 (male connector EN 175301-803 )
IP 67 (M12x1 male connector)
8 .. 30 V DC 2 conductor
12 .. 30 V DC 3 conductor
- limited energy- according to 9.3 UL 61010; Class 2;
UL 1310/1585; LPS UL 60950
≤ 5 %
≤ 25 mA
> 10 million cycles (0 .. 100 % FS)
~ 150 g
HYDAC ELECTRONIC GMBH
4
6
10
16
25
12
20
32
50
80
18
30
48
75
120
R
= (U
– 8 V) / 20 mA [kΩ]
Lmax
B
R
= 2 kΩ
Lmin
HDA 4700
≤ ± 0.25 % FS typ.
≤ ± 0.5 % FS max.
≤ ± 0.15 % FS typ.
≤ ± 0.25 % FS max.
≤ ± 0.008 % FS / °C typ.
≤ ± 0.015 % FS / °C max.
≤ ± 0.008 % FS / °C typ.
≤ ± 0.015 % FS / °C max.
≤ ± 0.3 % FS max.
≤ ± 0.1 % FS max.
≤ ± 0.08 % FS max.
≤ 1 ms
≤ ± 0.1 % FS / year typ.
30 .. +85 °C / -25 .. +85 °C
HDA 4700 / 4400 with flush membrane
40
60
100
250
80
120
200
500
200
300
500
1000
Part no.: 669872
400
600
800
900
2000
2000