2.6. Specifications tables

DC inputs
Recommended power range of PV array
Maximum input voltage
(2)
MPP Voltage range
Operating voltage range
Minimum voltage for Pnom
Maximum short circuit current
Maximum inverter backfeed current to the PV array.
MPPT
Number of strings
Maximum input current
Maximum input current per string
AC output
Rated power
Maximum continuous power
Max. temperature for nominal power
Maximum current
Inrush current
Maximum output fault current
Maximum output overcurrent protection
Rated voltage
Voltage range
Nominal frequency
Cosine of Phi
Adjustable cosine of phi
THD
Performance
Maximum efficiency
Euroefficiency

General data

Cooling system
Air flow
Weight
Dimensions (height x width x depth)
Stand-by consumption
(4)
Night consumption
Operating temperature
Relative humidity (without condensation)
Maximum altitude of the installation
Protection class
Markings
EMC and safety regulations
Grid connection regulations
(1)
Depending on the type of installation and the geographic location.
panels 'Voc' at low temperatures.
Only for inverters with outputs up to 16 A.
(5)
70
11TL
11.3 ~ 14.8 kWp
(1)
1000 V
560 ~ 820 V
560 ~ 1000 V
560 V
40.7 A
31.9 A rms
37 A
11 A
11 kW
11 kW
55 ºC
(3)
29 A
29 A
< 31.9 A rms (60 ms)
31.9 A rms
220 V
187 ~ 528 V
50 / 60 Hz
Yes. Smax = 11 kVA
Qmax = 11 kVAR
< 3 %
98.5 %
98.3 %
200 m
46.8 Kg
< 10 W
1 W
–25 ~ +65 ºC
0 ~ 95 %
4000 m
IP65
EN 61000-6-1, EN 61000-6-2, EN 61000-6-3, EN 61000-6-4, EN 61000-3-11, EN 61000-
3-12, EN 62109-1, EN 62109-2, IEC62103, EN 50178, FCC Part 15, AS3100
RD1699/2011, DIN V VDE V 0126-1-1, EN 50438, CEI 0-16 Ed.III, CEI 0-21, VDE-AR-N
4105:2011-08, G59/2, G83/2
UNE 206007-1, ABNT NBR 16149, ABNT NBR 16150, South African Grid code, Chilean
Grid Code, Romanian Grid Code, Ecuadorian Grid Code, Peruvian Grid code, IEEE 929,
Thailand MEA & PEA requirements, DEWA (Dubai) Grid Code, Jordan Grid Code
For each ºC of increase, the output power is reduced by 1.8 %.
(3)
20TL
20.5 ~ 26.1 kWp
1000 V
560 ~ 820 V
560 ~ 1000 V
560 V
40.7 A
31.9 A rms
1
1
1
1
37 A
11 A
20 kW
20 kW
55 ºC
29 A
29 A
< 31.9 A rms (60 ms)
31.9 A rms
400 V
187 ~ 528 V
50 / 60 Hz
1
1
Yes. Smax = 20 kVA
Qmax = 20 kVAR
< 3 %
98.5 %
98.3 %
Forced ventilation
/h
200 m
3
46.8 Kg
730 x 700 x 250 mm
< 10 W
1 W
–25 ~ +65 ºC
0 ~ 95 %
4000 m
IP65
CE
, P.O.12.3, AS4777.2, AS4777.3, IEC 62116, IEC 61727,
(5)
(2)
Never exceed this value. Consider the voltage increase of the
ABO2011IQM01_C - Installation and Operation Manual
Unit description
33TL
34 ~ 45 kWp
1000 V
560 ~ 820 V
560 ~ 1000 V
560 V
67.1 A
52.8 A rms
1
1
61 A
11 A
33 kW
33 kW
45 ºC
48 A
48 A
< 52.8 A rms (60 ms)
52.8 A rms
400 V
304 ~ 528 V
50 / 60 Hz
1
Yes. Smax = 33 kVA;
Qmax = 20 kVAR
< 3 %
98.3 %
97.9 %
/h
400 m
/h
3
3
51.5 Kg
< 10 W
1 W
–25 ~ +65 ºC
0 ~ 95 %
4000 m
IP65
Consumption from the PV array.
(4)