10.11. Configuring the cosine of phi

By changing the cosine of phi you can regulate the reactive power injected into the grid.
To change the cosine of phi, access Main menu > Advanced settings > CosPhi reference. Beside the cosine value,
you can indicate its sign: positive or negative.
The inverter is configured with the selected cosine of phi. If the inverter receives instantaneous setpoints via the
communication, the cosine of phi value indicated in these setpoints prevails.

10.12. Configure the inverter to work in self consumption mode

These inverters can work within a self consumption system. For this, you must configure the inverter for self
consumption system mode.
Access Main menu > Advanced settings > Self consumption > Mode to select the self consumption mode.
There are different self-consumption modes: No limitation (MPPT), Limited EMS manager and Self-limited CG
EM24.
Without limitations (MPPT) Self consumption mode without limits of injecting into the grid.
Limited EMS manager
Self-limited CG EM24
10.13. Configure the inverter to work in a grid with diesel
generator.
If the inverter is part of a diesel generator system, this must be specifically configured. For this configuration
access Main menu > Advanced settings > Country regulations > Diesel grid. Once selected Diesel grid configure the
desired voltage and frequency.

10.14. Place the inverter in operating mode

To start the inverter in operating mode access Main menu > Start/Stop. This screen display's the inverter's current
status and enables, via a keypad
operating.

10.15. Place the inverter in stop mode

To place the inverter in stop mode access Main menu > Start/Stop. This screen display's the inverter's current
status and enables, via a keypad
to stopped.

10.16. See the daily power graph

The daily power graph displays the power generated throughout the current day. To see this graph, from the main
screen press
. Besides the daily power graph it lists the daily energy values (Ed), from the first connection of the
day to the time of consultation, total energy (Et) from the first inverter connection* and the instantaneous power
(P).
* This historical meter returns to zero if reset to default settings.
102
Limited self consumption mode via the INGECON EMS Manager. For installations with
several inverters.
Instantaneous self consumption mode limited by a wattmeter. For installations with a
single inverter.
, changing the status. If the current status is stopped, press
, changing the status. If the current status is operating, press
2019-07-09
2019-07-09
10:17
10:17
ABO2011IQM01_C - Installation and Operation Manual
Display control
to change it to
to change it

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Ingecon sun 3play 11tlIngecon sun 3play 20tlIngecon sun 3play 33tlIngecon sun 3play 11tl mIngecon sun 3play 20tl mIngecon sun 3play 33tl m ... Afficher tout

Table des Matières