Maintenance Work; Inspection Intervals - Burkert 2730 Manuel D'utilisation

Vanne de réglage à membrane commandée par piston
Masquer les pouces Voir aussi pour 2730:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Type 2730 / 2731 / 2731K
Maintenance,cleaning
10.2 Maintenance work
10.2.1 Actuator
The actuator of the diaphragm control valve is maintenance-free
provided it is used according to these operating instructions.
10.2.2 Wearing parts of the diaphragm
control valve
Parts which are subject to natural wear:
• Seals
• Diaphragm
If leaks occur, replace the particular wearing part with an appro-
priate spare part (see chapter "12 Replacement parts").
A bulging PTFE diaphragm may reduce the flow.
The replacing of the wearing parts is described in chapter
"11 Repairs".
10.2.3 Inspection intervals
Check diaphragm for wear after maximum 10
Muddy and abrasive media require correspondingly shorter

inspection intervals!

10.2.4 Service life of the diaphragm
The service life of the diaphragm depends on the following factors:
• Diaphragm material
• Medium, Medium pressure, Medium temperature
• Actuator size
• Pilot pressure for CFB.
Protecting the diaphragm
For CFA match the actuator size (actuator force) to the medium
pressure to be actuated. If required, select the actuator with
reduced spring force EC04.
For CFB try and select the pilot pressure not higher than is
required to actuate the medium pressure.
10.2.5 Cleaning
Commercially available cleaning agents can be used to clean the
outside.
NOTE!
Avoid causing damage with cleaning agents.
▶ Before cleaning, check that the cleaning agents are compatible
with the body materials and seals.
switching cycles.
5
english
23

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

27312731k

Table des Matières