Technical Data; Intended Use; Product Data; Type Key - Wilo SiFire EN Série Notice De Montage Et De Mise En Service

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

3.1 Residual risk during transport and storage

WARNING! Risk of Cut!
Sharp edges or any not protected threaded parts
entail the risk of getting cut.
Take necessary cautions to avoid injuries and
use protective equipment (wear specific
gloves).
WARNING! Risk of personal injury!
Do not stand or put members under the sus-
pended parts during handling and installation.
Use clothing dedicated to protection against
accidents (wear helmet and safety shoes).
WARNING! Risk of impact!
Be careful of prominent parts and parts at head
level. Use clothing dedicated to protection
against accidents.
DANGER! Risk of fall!
Prohibit access to wells or tanks, where pumps
are installed. Wells must have closing cover.
WARNING! Risk of irritation!
During handling, avoid spillage of battery acid
solution which could cause irritations or mate-
rial damages. Use special protections to avoid
contact.
CAUTION! Risk of environmental pollution!
Avoid dumping of oil from the engine or diesel
fuel from the tank. During handling, keep them
flat. Use suitable protection and implement the
necessary measures to prevent pollution of soil,
water, etc.
5.2

Technical data

Maximum operating pressure:
Maximum ambient temperature:
Maximum water temperature:
Supply voltage:
Frequency:
Maximum relative humidity:
Protection class of Control box:
Protection class of pump:
Motor IE2 insulation class:
Maximum altitude for installation:
Minimum atmospheric pressure:
Nominal current:
(*) Seen the specific graphs and tables in the catalogues and maintenance manuals for the details of class variations for electric machines and diesel engines with
regard to different temperatures, altitudes, atmospheric pressure, fuel temperature and viscosity compared to standard test conditions.
Installation and operating instructions Wilo-SiFire System

4 Intended use

The fire extinguishing boosters are designed for a
professional use. They are used when an increase
or a maintaining under pressure of the fire net-
work is necessary.
The system must be installed in a special room
which is protected from frost and rain, fireproof
and ventilated enough, with necessary spaces
around pumps for movements and regular main-
tenance .The room must be in accordance with the
EN 12845 standards. Airflow for ventilation and
for cooling of engines, more specifically diesel

5 Product data

engine -if present- has to be sufficient.

5.1 Type key

Example
SiFire EN 40-200 180 7,5/10.5/0.55 EDJ
SiFire
Name of the Fire Extinguishing System
EN
In accordance with EN 12845 standards
40/200
Type of main pump
180
Impeller diameter of main pump
7,5/10.5/
Nominal power of the pump motors [kW]
0.55
(electrical motor/diesel engine/jockey motor)
EDJ
Configuration:
E
D
EJ : 1 electric pump + 1 jockey pump
EEJ : 2 electric pumps + 1 jockey pump
EDJ : 1 electric pump + 1 diesel pump + 1 jockey
DJ : 1 diesel pump + 1 jockey pump
10 bar/16 bar according to the pump
+4 to +40 °C (10 to 40°C if diesel pump is installed)
+4 to +40 °C
3~400 V ± 10 %
(1~230 V ± 10 %, for diesel pump control panel)
50 Hz
50 % with Tmax.: 40 °C (*)
IP54
IP54
F
1000 m above sea level (*)
760 mmHg (*)
refer to the rating plate
: 1 electric pump
: 1 diesel pump
pump
English
31