Description
Transducer
The PENTEK INTELLIDRIVE uses a 4-20mA,
0-100PSI pressure transducer to control motor
speed (max is 300 PSI transducer).
The transducer (see Figure 1) senses pressure in
the pipe and converts it to an electrical signal.
The Drive senses and processes the signal in the
PID (Proportional, Integration, Derivative) control.
When operating in AUTOSTART mode, the Drive
increases and decreases the speed of the pump
motor as needed to maintain constant pressure in
the piping system.
Changes internal pressure setpoint from
15 PSI to transducer max -3PSI
(default is 60 PSI).
Runs the Drive at 45Hz (with no
pressure control) to allow installer to
Changes display to previous screen.
Selects menu items and confirms
numeric value changes.
Power is ON to Drive.
Drive is in Warning Mode (TPM); refer to
Troubleshooting section.
A fault has occurred.
Displays Drive's current operating
condition and changes display
Figure 2 - PENTEK INTELLIDRIVE keypad functions
pump out well.*
parameters.
Stops the motor.
Keypad
The keypad programs the Drive, monitors the status
of the pump, and displays faults if they occur.
Each button has a unique function, as described in
Figure 2. The LCD display shows a text display of
the status of the Drive's operation. Other LEDs light
up to indicate when certain buttons are pressed or
certain events occur.
Fan
The Drive uses a thermostatically controlled
internal fan which operates automatically when
necessary to cool the Drive components.
Views and changes parameters.
Shows last 15 faults.
With code, locks and unlocks password
protected keys.
Toggles between English, Spanish, and
French (default is English).
Left and right arrows move cursor.
Up and down arrows scroll through
menus and change numeric values.
Resets fault that stopped Drive/pump.
Checks for line fill, then starts pump in