ELECTRICAL CONNECTIONS
Use ßexible cables according to EN 60 335-1
Regulations:
¥ if in PVC sheath, use at least H05 VV-F
¥ if in rubber sheath, use at least H05 RR-F.
All the wires to connect to the burner plugs 7)(A)
must enter through the supplied fairleads, which
must be Þtted into the relevant holes in the left
hand or right hand plate. To do this, Þrst unscrew
screws 8), then split the plate into its parts 9)
and 10) and remove the menbrane press-outs
from the holes.
The fairleads and hole press-outs can be in var-
ious ways; the following lists show one possible
solution:
RS 28 und RS 38 single-phase
1 - Pg 11
Single-phase power supply
2 - Pg 11
Gas valves
(when RG1/CT or LDU 11 leak
detection control device is not Þtted)
3 - Pg 9
Remote control device TL
4 - Pg 9
Remote control device TR
5 - Pg 11
Gas pressure switch or gas valve
leak detection control device
RS 38 three-phase and RS 50
1 - Pg 11
Three-phase power supply
2 - Pg 11
Single-phase power supply
3 - Pg 9
Remote control device TL
4 - Pg 9
Remote control device TR
5 - Pg 11
Gas valves
(when RG1/CT or LDU 11 leak
detection control device is not Þtted)
6 - Pg 11
Gas pressure switch or gas valve
leak detection control device
LAYOUT (B) - The RS 28 - 38 Models electrical
connection single-phase power supply
without leak detection control device.
LAYOUT (C) The RS 28 - 38 Models electrical
connection single-phase power supply
with VPS leak detection control device.
Gas valve leak detection control takes place
immediately before every burner start-up.
LAYOUT (D) The RS 28 - 38 Models electrical
connection single-phase power supply
with RG1/CT RIELLO or LDU LANDIS leak
detection control device.
Gas valve leak detection control takes place
immediately before every burner start-up.
Key to layouts (B - C - D)
h1 - 1st stage hourcounter
h2 - 2nd stage hourcounter
IN - Burner manual stop switch
XP- Plug for leak detection control device
X4 - 4 pole plug
X6 - 6 pole plug
X7 - 7 pole plug
PC- Gas pressure switch for leak detection con-
trol device
PG- Min. gas pressure switch
S - Remote lock-out signal
S1 - Remote lock-out signal of leak detection
control device
TR- High-low mode load remote control system:
controls operating stages 1 and 2.
If the burner is to be set up for single stage
operation, replace of remote control device
TR with a jumper.
TL - Load limit remote control system:
shuts down the burner when the boiler tem-
perature or pressure reaches the preset
value.
TS - Safety load control system:
operates when TL is faulty
VR- Adjustment valve
VS- Safety valve
BRANCHEMENTS ELECTRIQUES
Utiliser des c‰bles ßexibles selon la norme EN
60 335-1:
¥ si en gaine PVC, au moins type H05 VV-F
¥ si en gaine caoutchouc, au moins type H05
RR-F.
Tous les c‰bles ˆ raccorder aux Þches 7)(A) du
bržleur doivent par les passe-c‰bles de sŽrie ˆ
insŽrer dans les oriÞces pratiquŽs dans la pla-
que, de gauche ou de droite, aprŽs avoir des-
serrŽ les vis 8), ouvert la plaque (parties 9 et
10) et retirŽ le Þn diephragme recouvrant les
trous. L'utilisation des passe-c‰bles et des trous
prŽdŽcoupŽs peut se faire de plusieurs fa•ons;
ˆ titre d'exemple nous indiquons l'une de ces
possibilitŽs:
RS 28 et RS 38 monophasŽs
1 - Pg 11
Alimentation monophasŽe
2 - Pg 11
Vannes gaz
(lorsque le contr™le d'ŽtanchŽitŽ
RG1/CT ou LDU 11 n'est pas montŽ)
3 - Pg 9
TŽlŽcommande TL
4 - Pg 9
TŽlŽcommande TR
5 - Pg 11
Pressostat gaz ou contr™le d'Žtan-
chŽitŽ vannes gaz
RS 38 triphasŽ et RS 50
1 - Pg 11
Alimentation triphasŽe
2 - Pg 11
Alimentation monophasŽe
3 - Pg 9
TŽlŽcommande TL
4 - Pg 9
TŽlŽcommande TR
5 - Pg 11
Vannes gaz
(lorsque le contr™le d'ŽtanchŽitŽ
RG1/CT ou LDU 11 n'est pas montŽ)
6 - Pg 11
Pressostat gaz ou
contr™le d'ŽtanchŽitŽ vannes gaz
SCHEMA (B) - Alimentation monophasŽe
Branchement Žlectrique bržleurs RS 28 - 38
sans dispositif de contr™le d'ŽtanchŽitŽ.
SCHEMA (C) - Alimentation monophasŽe
Branchement Žlectrique bržleurs RS 28 - 38
avec dispositif de contr™le d'ŽtanchŽitŽ VPS.
Le contr™le d'ŽtanchŽitŽ des vannes se fait juste
avant chaque mise en marche du bržleur.
SCHEMA (D) - Alimentation monophasŽe
Branchement Žlectrique bržleurs RS 28 - 38
avec dispositif de contr™le d'ŽtanchŽitŽ
RG1/CT RIELLO ou LDU LANDIS.
Le contr™le d'ŽtanchŽitŽ des vannes se fait juste
avant chaque mise en marche du bržleur.
Legende schemas (B - C - D)
h1 - Compteur dÕheures 1•re allure
h2 - Compteur dÕheures 2•me allure
IN - Interrupteur Žlectrique pour arr•t manuel
bržleur
XP- Fiche pour le contr™le d'ŽtanchŽitŽ
X4 - Fiche 4 p™les
X6 - Fiche 6 p™les
X7 - Fiche 7 p™les
PC- Pressostat gaz pour contr™le dÕetanchŽitŽ
PG- Pressostat gaz seuil minimum
S - Signalisation blocage bržleur ˆ distance
S1 - Signalisation blocage contr™le d'ŽtanchŽitŽ
ˆ distance
TR- TŽlŽcommande de rŽglage:
commande 1•re et 2•me allure de fonc-
tionnement.
Si l'on dŽsire un bržleur ˆ fonctionnement ˆ
une seule allure, remplacer TR par un pontet.
TL - TŽlŽcommande de limite:
arr•te le bržleur quand la tempŽrature ou la
pression dans la chaudi•re a atteint la
valeur ÞxŽe.
TS - TŽlŽcommande de sŽcuritŽ:
intervient quand le TL tombe en panne
VR- Vanne de rŽglage
VS- Vanne de sŽcuritŽ
21