Télécharger Imprimer la page

CEMO DT-Mobil PRO ST 980 l Mode D'emploi page 50

Publicité

GB
7. Maintenance and inspection
7.1
Safety measures
i
Important!
The operator must provide any protective clothing that may be required.
Who can carry out maintenance and inspection work?
» Normal maintenance work can be carried out by trained operating personnel.
i
Important!
Inspections of the filling station with regard to ADR approval may only be performed by a recog-
nised, registered inspection agency.
7.2
Maintenance and inspection table
Interval
Assembly
Outside of the
If required
filling station
Container
Every
month
Piping system
Moving parts of
the tank
Every year
Leak detector
Every 2½
Filling station
years
Every 5
Filling station
years
7.3
Troubleshooting
Fault
The pump is not delivering
The pump is not delivering
much
50
Action
Clean off any dirt or diesel residue.
Repair damage to the galvanisation through cold galvanisation or damage
to the paintwork with 2K PU paint RAL 7036 "platinum grey".
Visual check for damage
Check hoses for cracks and porosity, check fittings for leaks (replace
defective parts).
Lubricate hinges and lock with a few drops of universal oil.
Perform visual inspection and performance test as described in the opera-
ting instructions for leak detector LS-03.
Inspection according to ADR 6.5.4.4.1 b) and 6.5.4.4.2
- Documentation in the test report (see section 10)
- For successful inspection – Imprint on type plate (month/year)
Inspection according to ADR 6.5.4.4.1 a) and 6.5.4.4.2
- Documentation in the test report (see section 10)
- For successful inspection – Imprint on type plate (month/year)
Possible cause
The delivery line ball valve is
closed
The hoses are blocked or
buckled
Air bubbles in the liquid
DT-Mobil PRO ST only:
Filter blocked
Solution
Open the ball valve
Check the hoses
Let the tank rest for a few minutes
Clean filter (see section 7.4)

Publicité

loading

Ce manuel est également adapté pour:

Dt-mobil pro pe 980 lDt-mobil easy 980 l