6.10.3 - CT10324 ADVANCED MENU (ADV)
The ADVANCED MENU allows the system to be further customised by
modifying parameters not accessible from the basic menu.
To access the ADVANCED menu, press the MENU key and hold it
down for 5 seconds.
CT10324
1
foto1 setup
2
foto2 setup
3
photo test
4
type edge
5
setup edge
6
test edge
7
flash setup
20
OLD
CT10224
Defines the behaviour of the automation, starting from
the closed position
SP.h.
0 = if PH1 is engaged, no opening command is executed
1 = if PH1 is engaged, it still executes the opening
command
Checking the engaged status of PH2
0 = active during both the opening and closing
Ph.2.
manoeuvres
1 = only active during the opening manoeuvre
Photocell functionality test
0 = no test
1 = checks the functionality of the photocells connected
to the PH1 terminal
tP.h.
2 = checks the functionality of the photocells connected
to the PH2 terminal
3 = checks the functionality of the photocells connected
to the PH1 and PH2 terminals
Defines the type of safety connected to the EDGE/
STOP terminals
0 = STOP NC contact
Ed.m.
1 = 8k2 safety edge
2 = sensitive edge NC
3 = 4k1 safety edge
(two safety edges in parallel)
Defines the situations in which the intervention of the
safety edge connected to the EDGE/STOP inputs
should be evaluated.
0 = EDGE/STOP input status evaluated only during
the closing manoeuvre
iE.D.
1 = EDGE/STOP input status evaluated during both the
closing and opening manoeuvres
ATTENTION !
input during an opening manoeuvre results in a
brief reversal; during a closing manoeuvre, on the
other hand, it results in a full opening manoeuvre.
Edge test
tE.D.
0 = off
1 = on
Defines the behaviour of the FLASH output
0 = output always active during opening closing and
manoeuvres
1 = output flashing during opening and closing
manoeuvres
2 = output always active with barrier in open position
3 = electrical lock (12V); before performing the opening
manoeuvre, the output is activated for the time set in
the ELECT TIME parameter (ADV menu)
4 = magnetic lock (24V); output active when the barrier
is closed, the ELECT TIME parameter specifies
FP.r.
the demagnetisation time before starting the opening
manoeuvre.
ATTENTION !
with 24VDC winding
5 = output active for fault signalling: motor
over-travel, encoder error, limit switch error, three
impacts were detected that prevented arrival at the
limit switch, number of manoeuvres indicated by the
parameter CYCLE SERVI exceeded.
NOTE: to deactivate an active signal, the equipment
must be powered off
To modify ADVANCED MENU parameters, proceed as described for
the BASIC MENU.
N.B: Some default functions/displays may vary depending on the type
of motor selected.
DESCRIPTION
Intervention of the EDGE/STOP
equires an external relay
DEFAULT
MIN
MAX
1
0
1
0
0
1
0
0
3
1
0
3
0
0
1
0
0
1
1
0
5
UNIT