SAFETY AND CONTROL DEVICE CONNECTORS
24 VAC
Accessory power supply 24VAC without regulation, 200mA MAX; not active during battery operation
COM
Positive common for FLASH - IND/ELEC - LED outputs and accessories
FLASH
Flashing light output 24Vdc (without regulation), maximum 15W
IND output for barrier open indicator light 24 Vdc not regulated 5W MAX / Electric lock output 12Vac, 15VA maximum
IND/ELEC
selectable with parameter indic light
LED
Courtesy light output 24Vdc (without regulation), maximum 15W, controllable also via radio ON-OFF command
NEG
Power supply for accessories, negative
PH-POW
Positive power supply for PH1 and PH2 photocells; operating mode configurable via the PHOTO TEST parameter
EDGE/STOP
Safety edge 8k2/NC contact input; operating mode configurable with the EDGe parameter
ATTENTION !
EDGE/STOP
PH2 opening photocell NC input; at any moment during opening, the activation of the photocell (opening of the
contact) causes the movement to stop immediately. Opening is reset when the contact closes. Operating
PH2
modes are configurable with the PHOTO 2 SETUP parameter
ATTENTION !
PH1 closing photocell NC input; at any moment during closing, the activation of the photocell (opening of the contact) immedi-
ately stops the movement and reverses the direction of travel. Opening is reset when the contact closes. The operating modes
PH1
can be configured via the PHOTO 1 SETUP parameter
ATTENTION !
OPEN
OPENING command NO input; MAN PRESENT function configurable via the HOLD TO RUN parameter
CLOSING command NO input; by keeping the input active (closed), the SBS, OPEN and PAR commands are inhibited; MAN
CLOSE
PRESENT function configurable via the HOLD TO RUN parameter
STEP-BY-STEP command NO input; each time it is activated, the commands OP (open) - ST (stop) - CL (close) are executed
PAR
in sequence. The operating modes can be configured via the SBS SETUP parameter; MAN PRESENT function configur-
able via the HOLD TO RUN parameter
SBS
Positive common for PH2, PH1, OP, CL, PAR, SBS inputs
COM
Antenna - shield
SHIELD
Antenna - shield
ANT
Antenna - signal
6.5 - Disabling the safety devices
EDGE
The control unit provides (default setting) for the installation of a safety edge connected to the EDGE/STOP inputs; in the event of a missing or
incorrect connection, the operation of the automation is inhibited. In a system where a safety edge is not to be installed, its use can be disabled
by setting the EDGE dip-switch to ON.
ATTENTION !
confirm the safety edge deactivation by pressing and holding the buttons
PHOTO 2
The control unit provides (default setting) for the installation of one or more photocells connected to the PH2 input, in the event of a missing
or incorrect connection, the operation of the automation is inhibited. In a system where a PH2 is not to be installed, its use can be disabled by
setting the PH2 dip-switch to ON.
ATTENTION !
confirm the PH2 deactivation by pressing and holding the buttons
PHOTO 1
The control unit provides (default setting) for the installation of one or more photocells connected to the PH1 input, in the event of a missing or
incorrect connection, the operation of the automation is inhibited. In a system where a PH1 is not to be installed, its use can be disabled by setting
the PH1 dip-switch to ON.
ATTENTION !
confirm ph1 input deactivation by pressing the
stops flashing.
.
with the EDGE dip switch set to ON, the input is always disabled
with the PH2 dip switch set to ON, the input is always disabled
with the PH1 dip switch set to ON, the input is always disabled
and
and
until the edge LED stops flashing.
and
until the PH2 LED stops flashing.
buttons simultaneously and holding them down until the ph1 led
EN
13