Setting According To The Batteries Type; Temperature Compensation - Cristec YPOWER 12V/16A Manuel Utilisateur

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 1

3.3.2 Setting according to the batteries type

Switches setting
A
B
C
D
0
0
0
0
1
0
0
0
0
1
0
0
1
1
0
0
0
0
1
0
1
0
1
0
0
1
1
0
1
1
1
0
0
0
0
1
1
0
0
1
0
1
0
1
0
1
1
1
1
1
1
1
(*) Voltage on + BAT 1, + BAT 2 and + BAT E with 10% of the rated current and a tolerance of +/- 1%.
The voltages values must be doubled for 24V batteries .
(
)
**
REFRESH is not advised for certain types of AGM batteries
(***) Battery Management System
Some specific settings are possible – please consult us.

3.3.3 Temperature compensation

The STP-NEW-2.8 probe enables the compensation of Absorption voltage and
Floating Voltage depending on the ambient temperature of the battery room.
The coefficient used is -3mV/°C/element.
Description of the
battery type
Opened type bat
free electrolyte (wet)
Classic sealed type
bat
(Sealed Lead)
GEL type bat
AGM type bat**
Spiral type bat
Tin calcium lead bat
Wintering or standby
sealed bat
Stabilized DC power
supply
SPE1 open type bat
Lithium Iron Phosphate
( LiFePO4 ) with BMS
(***)
STORMLINE Bat
Voltage* with
Voltage* with
BOOST OFF
BOOST ON
13.4V
14.1V
13.8V
14.4V
FACTORY SETTING
13.8V
14.4V
13.6V
14.4V
13.6V
14.4V
14.4V
15.1V
13.4V
13.4V
12.0V
12.0V
13.2V
14.8V
13,8V
14,4V
13,7V
14,5V
Booked
Booked
Maximum
Maximum
duration of
duration of
BOOST at
ABSOPTION at
+/- 5% T
+/- 5% T
BOOST
2H
4H
2H
4H
2H
4H
2H
4H
2H
4H
2H
4H
0H
0H
0H
0H
2H
4H
6H
10H
2H
6H
ABS