Cables for analogue display units: reference DEP-V-A-CPS2
For connecting analogue voltmeter options (1 to 4 depending on the number of outputs to be
monitored: Bat D, Bat 1, Bat 2 or the voltage upstream of the distributor) and an ammeter
A 5-meter cable; connect to K10 (see drawing in appendix)
48x48mm analogue voltmeter to view the voltage of a particular output or the charger's voltage
upstream of the distributor
Reference: VLT0024-CPS2 for 24Vcc chargers
Connect to K10 with option DEP-V-A-CPS2
48x48mm analogue voltmeter to view the charger's total current; connect to K10 with option
DEP-V-A-CPS2
Model
CPS2 OEM / 24 - 40
Remote LEDs option: reference LED-DEP-CPS2
A 5-metre cable to connect on KLD1/KLD2/KLD3
5

COMMISSIONING

This paragraph lists all the tasks required to bring the equipment into service.
These instructions should be followed to the letter before first turning on the appliance.
5.1

ELECTRICITY NETWORK

The CPS2 OEM 24V/40A chargers can operate automatically and equally on single-phase networks from 85 to 265VAC
and from 47 to 63Hz.
Generators
The Cristec battery charger is designed to operate on a generator. In certain cases, generators can produce high surges.
Before connecting the charger, check its compatibility with the generator's characteristics: power, voltage, surges,
frequency, current etc.
Power limiting switch
A switch on the outside of the case (the cable lead-in side) limits the charger's output power (on position 1) :
This may prevent the differential circuit-breaker at the beginning of the 230/115VAC line from tripping.
5.2

CHARGER COMPATIBILITY AND SETTINGS ACCORDING TO BATTERY TYPE

Before switching on, be sure to check the compatibility of voltage, current and settings according to the type of
connected.
Checking the load voltage
Before connecting the batteries to the charger, you must check the polarity of the accumulators. Also check the voltage of
the batteries with the aid of a calibrated voltmeter. A low voltage on certain types of accumulators may indicate they have
sustained irreversible damage, thereby precluding any possibility of recharging.
CPS2OEM24V-40ADEB.DOC
Reference
AMP 24V/50A CPS2
Charger
CPS2 OEM / 24 - 40
Rated power =
Input current
90%
< 6A
batteries