Setting conditions: the product is set in app mode, and all States can be set. explain:
LWD:Low Watt Discharge
In inverter mode, the setting of low power discharge time is 8 (8 hours) by default, and the range can
be set [1, 8].
In battery mode, if the battery shutdown point is not reached after continuous discharge for more
than 8 hours, the battery voltage shutdown point will be modified to 11V * number of battery cells.
When the battery is discharged to 11V * number of battery cells, the system will alarm for 1 minute
and then shut down.
When the battery voltage exceeds 13.2v * the number of battery cells exceeds 30s, the battery
discharge time will be reset.
Product soft start setting
SRE
Figure 1-35 product soft start setting page
Function Description: when the interface is on, the product output gradually increases from 0 to the
target voltage value. When the interface is off, the product output directly increases from 0 to the
target voltage value.
Setting conditions: all States can be set. explain:
SRE:Soft Relay Enable
The default setting is off, and the output switch will not be closed until the product voltage rises to
the rated output. If it is set to on, the output switch will be closed before the product starts boosting.
Default settings
SED
Figure 1-36 default value setting page
Function Description: restore all settings to the default value.