Figure 1-32 setting page of mains low voltage point in product mode
Function Description: set the low-voltage protection point of mains power. Setting conditions: the
product is in app and UPS mode, and all States can be set. explain:
LLV:Line Low Voltage
In inverter mode (output mode: Mod needs to be set to APP), the low-voltage point of mains power
is set, the default setting is 154v, and the settable range is [90154]. (output mode: Mod needs to be
set as UPS), the low-voltage point of mains power is set, the default setting is 185v, and the settable
range is [170200].
Setting of mains high voltage point
LHV
(
)
Figure 1-33 setting page of mains high voltage point in inverter mode
Function Description: set the high-voltage protection point of mains power. Setting conditions: the
product is in app mode, and all States can be set. explain:
LHV:Line High Voltage
In inverter mode (output mode: Mod needs to be set as app), the high voltage point of mains power
is set. The default setting is 264v, and the settable range is [264280].
Low power discharge time setting
LWD
(
)
Figure 1-34 low power discharge time setting page
Function Description: low power discharge protection function. When the battery is in a low load
mode, unlimited discharge will empty the battery and affect the battery life. When the product is in
the low power discharge setting time, the low voltage shutdown point of 3k-vml-24v battery will be
increased to 22V. The low-voltage shutdown point of 5k-vmh-48v battery will be increased to 44V.