Constant voltage mode voltage point setting
Function Description: constant voltage point setting function. Setting conditions: all States can be set.
explain:
bCV:battery Constant Voltage
It cannot be set when the battery definition mode is AGM (lead-acid battery type) or FLD (water
injection battery type). The initial default settings of 3k-vml-24v are 28.2v (AGM) and 29V (FLD)
The initial default settings of 5k-vmh-48v are 56.4v (AGM) and 58V (FLD)
When the battery type is set to cus (customer setting type), the constant voltage charging point can
be modified.
3k-vml-24v can be set to [24,29]. The voltage at the constant voltage point needs to be greater
than the voltage at the floating charge point.
5k-vmh-48v can be set to [48,60]. The voltage at the constant voltage point needs to be greater
than the voltage at the floating charge point.
When the battery type is set to Lib (lithium battery type), the constant voltage charging point can be
modified.
The default setting of 3k-vml-24v is 28.2, and the settable range is [25,29]. The voltage at the
constant voltage point needs to be greater than the voltage at the floating charge point.
The default setting of 5k-vmh-48v is 56.4, and the settable range is [48,60]. The voltage at the
constant voltage point needs to be greater than the voltage at the floating charge point.
Floating charge mode voltage point setting
EN
bCV
Constant voltage mode page figure 30-1