The default setting is on. After the main input detection is lost, the buzzer will sound for 3S; When set
to off, the buzzer will not sound normally after the main input is lost.
Energy saving mode
PWS
(
)
Figure 1-23 energy saving mode setting page
Function Description: set whether the product enables low power consumption mode (energy saving
mode). Setting conditions: all States can be set.
explain:
PWS:Power Saving
The default setting is off, and the function is not turned on; When set to on, in battery mode, if the
load is lower than 25W, the system will stop output briefly and then continue to output. If the load is
higher than 35W, the system will resume continuous normal output.
Overload to bypass
OLG
(
)
Figure 1-24 overload to bypass setting page
Function Description: when the battery mode is overloaded, set whether to switch to the mains
mode immediately (that is, the so-called bypass mode).
Setting conditions: all States can be set.
explain:
OLG:Overload to Bypass
The default setting is off, and the function is not turned on; When set to on, when the PV priority
output is loaded, if it is overloaded, the system will immediately switch to bypass (mains power
output, that is, the so-called bypass mode).