page of output voltage OPU. At this time, the word OPU is on for a long time, and the value flashes
to the right of the word OPU. Press the query key No. 2 or no. 3 key (three key screen: No. 2 key) for
0.1 to 2 seconds to select different output voltage values. The voltage values available for selection
are 208v, 220V, 230V and 240V. By default, the output voltage is 230V, and the settings are saved in
real time.
After turning the page to the output voltage value to be selected, press the confirmation key and No.
4 key for 0.1 to 2 seconds, and the output voltage OPU setting is completed. At this time, the value
on the right side of OPU is on for a long time and no longer flashes.
Press the No. 1 key for more than 0.1 to 2 seconds before the function setting is successful. Exit the
function setting page and return to the main display page (or do not operate, and automatically jump
back to the main display page after waiting for up to 30s).
be careful
:
When the output voltage is set to 208v, the output needs to be derated to 90%.
Other function settings Output frequency (OPF)
Output frequency setting, default 50Hz
Function Description: set the output frequency, 50Hz and 60Hz can be set, and the default is 50Hz.
Setting conditions: all States can be set, and the setting will take effect when the machine is
restarted next time in battery mode; The mains mode takes effect immediately. After setting, the
frequency will change slowly after switching back to battery mode.
Output priority setting (OPP)
EN
Figure 1-13 output frequency setting page