EN
Mute setting
MUE
(
)
Figure 1-25 mute setting page
Function Description: set whether the buzzer sounds. Setting conditions: all States can be set.
explain:
MUE:Mute
The default setting is off, and the function is not turned on; When set to on, the buzzer will not
sound in any case, alarm, fault and other states.
All modes can be set and function normally. Pictures cannot be displayed.
Battery back to mains voltage point
BTG
(
)
Figure 1-26 setting page of battery switching back to mains voltage point
Function Description: when the battery mains power exists at the same time, the battery will be
transferred to mains power when discharged to a certain voltage to ensure that the battery will not
be empty:
Setting conditions: all States can be set, and the output priority should be set in PV and PBG modes.
explain:
BTG:Back To Grid
The initial default setting of 3k-wml-24v is 23v The initial default setting of 5k-wmh-48v is 46v
When the battery definition mode is cus (customer setting type) mode:
3k-wml-24v can be set to [22,26] 5k-wmh-48v can be set to [44,52]
When the battery definition mode is AGM (lead-acid battery type) and FLD (water injection battery
type):
3k-wml-24v is set to 23v by default and can be set to [22,26]