Maintenance
The product is maintenance-free.
8.1
Use in flood hazard areas
The floating probe is suitable for use in flood hazard areas; it is watertight up
to 10 mH
2
9
Troubleshooting
Any malfunctions that cannot be removed by means of the measures
described in this chapter may only be repaired by the manufacturer.
Problem
Display does not show
anything
Red LED is on
Incorrect level indica-
tion
Other malfunctions
Maintenance
O (1 bar pressure).
Possible reason
No mains voltage
Mains fuse defective
Alarm condition
Line interruption in the
probe cable
Incorrect tank data
entered
-
Repair
Apply mains voltage
Replace the mains fuse
Remove the cause of
the alarm
Check the probe cable
Enter the tank data
again
Contact the AFRISO
service hotline
TankControl 10
EN E N
45