3. Select the threaded adapter (screw connector kit) suitable for the tank
connection.
Fig. 9: Cable gland kit
4. Push the threaded adapter onto the cable.
- Note the correct direction of the threaded adapter.
5. Perform zero calibration (see "Zero calibration of the submersible probe").
6. Push the submersible probe into the tank from the top.
7. Lower the submersible probe to the bottom of the tank.
8. At the cable gland, adjust the cable length of the probe cable in such a
way that the spacer reaches the tank bottom.
- Any volume of liquid below the the submersible probe is not detected by
the submersible probe.
9. Tighten the threaded adapter so that the probe cable can no longer be
moved
10.Determine the actual level (see "Displaying the level").
22
TankControl 10
Mounting
A) Cable gland for holding the measuring line
A
B) Connection thread (G½ and G1)
B
C) Threaded adapter (G1 to G1½)
D) Threaded adapter (G1½ to G2)
E) Bottom part
C
D
E