Télécharger Imprimer la page

afriso TankControl 10 Notice Technique page 77

Masquer les pouces Voir aussi pour TankControl 10:

Publicité

Les langues disponibles

Les langues disponibles

5.5.2
Connecting an additional submersible probe (optional)
1. Route the probe cable through the centre cable gland into the control
unit.
2. Connect the probe cable to "Sensor2" as follows:
- yellow/green to terminal "Shield"
- green to terminal "Signal"
- brown to terminal "AGND"
- white to terminal "Vcc"
3. Enable the additional probe in the software of the control unit (see "Set-
ting the password").
5.5.3
Connecting the floating probe (optional)
1. Route the probe cable through the centre cable gland into the control
unit.
2. Connect the probe cable to "Sensor2" as follows:
- Terminal "Signal"
- Terminal "AGND"
3. Enable the probe in the software of the control unit (see "Setting the
password").
Mounting
TankControl 10
EN E N
27

Publicité

loading