afriso TankControl 10 Notice Technique page 84

Masquer les pouces Voir aussi pour TankControl 10:

Publicité

Les langues disponibles

Les langues disponibles

EN
6.5.3
Setting the liquid level for submersible probe 2
1. Display the menu "Tankdaten 02".
2. Proceed as described in chapter "Setting the tank volume, tank height
and liquid level".
6.6
Zero calibration of the submersible probe
 Verify that the submersible probe is in air.
 Verify that the submersible probe is connected to the control unit.
 Verify that mains voltage is connected and switched on.
1. Set the value "Current level" to the value "000000 mm²" (see "Setting the
tank volume, tank height and liquid level").
2. The zero point of the submersible probe has been saved.
34
TankControl 10
Commissioning