10. WirinG
danger
risk of injury due to electrical discharge
• Shut down the electrical power source of all the
conductors and isolate it before carrying out work on
the system.
• Observe all applicable accident protection and safety
regulations for electrical equipment.
protect the power supply
• Protect the power supply with a correctly rated
fuse if it is not protected by default.
• Use a shielded cable with an operating tempe-
rature limit higher than +80 °C.
• Use a high quality electrical power supply (fil-
tered and regulated).
3
1
2
Fig. 4 : Pin assignment of the male fixed connector
English
28
Wiring of the SE30 Ex, marking ii 1
G/D or m1 (with nAmur intrinsic
safety barrier)
• Use a shielded cable with an operating temperature
suited to the process.
• Use an intrinsic safety barrier with NAMUR input and a
power supply, both complying with the safety instructions
and with the ATEX instructions notice.
• Earth the shielding of the cable on side of the
measuring exploitation.
• Before wiring the device, Plug out the female
connector.
L-
2
3
1
Fig. 6 : Wiring the SE30 Ex to an intrinsic safety barrier
English
30
1: V+ (12-36 V DC)
2: not connected
3: L- ( 0 V DC)
: Functional earth
-
+
L+
Assembling the female connector
→
Unscrew nut [1] of the cable gland.
2
→
Remove terminal block [3] from
housing [2].
→
3
Insert the cable into nut [1], through
seal [4], and into the cable gland and
finally through housing [2].
4
→
Connect the wires on terminal block
[3].
1
→
Position terminal block [3] in steps of
90° then put it back into housing [2],
pulling gently on the cable so that the
wires do not clutter the housing.
→
Tighten nut [1] of the cable gland.
→
Place seal [5] between the connector
and the fixed connector on the device
and then plug the 2508 connector into
5
the fixed connector.
→
Insert and then tighten screw [6] to
6
ensure tightness and correct electrical
contact.
Fig. 5 : Assembling the female connector type 2508
(supplied)
connection example with the
SE30 Ex and the externally
powered intrinsic safety barrier
Refer to the operation instructions of transmitter 8025
Universal for any other wiring instruction.
Position of 8025 Universal selectors:
• «SENSOR INPUT LOAD» = «1» (2.2 kΩ)
• «FLOW SENSOR» = «NPN/PNP»
• «SENSOR SUPPLY» = indifferent
English
29
29
English
31
31