Télécharger Imprimer la page

Ditel MICRA-M Manuel De L'utilisateur page 82

Masquer les pouces Voir aussi pour MICRA-M:

Publicité

Les langues disponibles

Les langues disponibles

KEYBOARD FUNCTIONS
Several functions can be controlled via keyboard that will produce different actions depending on the instrument
operating mode:
Mode -RUN-:
TARE and RESET TARE functions
Explained in the previous paragraph.
MAX/MIN function
Activated after pressing on the
by the instrument since the last time it has been switched on, unless a RESET MAX/MIN is done, the MAX led will
light up. A second press shows the minimum value in the same conditions as before, with the consequent
minimum indication through the MIN led.A third press bring the instrument back to the normal reading mode.
Function RESET MAX/MIN
Pressing continuously the
of the value. Will reset the minimum value if the same action is done while the instrument shows the valley value
(MIN).
ENTER 3s function (PROGRAMMING LOCKOUT)
In mode RUN if the ENTER key is pressed continuously during 3 seconds, the instrument will show the indication
CodE, and following 0000, allowing the user to introduce the security code. If the code that has been introduced is
wrong, the instrument will go back to RUN mode, if it is correct, it will allow the access to the security menu. See
paragraph 6 Page 34.
ENTER function
One press on the
key will bring the instrument to the -Prog- mode.
Mode -Prog-:
KEY
3s (RETURN TO FACTORY PROGRAMMING)
Allows entering a code of access to the reset of the configuration parameters, this code is 74. When entering this
code the instrument shows the LoAdIng dEFAuLt ConFIGurAtIon legend, following StorE, which means that they
have been stored in the non volatile memory of the instrument.
DIRECT ACCESS TO SETPOINTS – KEY
Now, in case any of the 2RE, 4RE, 4OP, 4OPP options has been installed, the instrument allows a direct access to
the programming of the setpoints value, pressing the
available according the option installed.
KOSMOS SERIE
key. From the normal reading mode, a press shows the maximum value read
during 3s., while the instrument shows the peak value (MAX), will produce a reset
Factory configuration
INPUT: Process 0 - 10V
DISPLAY
DISPLAY COLORS Run Mode: Green, Prog Mode.: Amber
SETPOINTS
ANALOG OUTPUT CONFIGURATION
LOGIC FUNCTIONS PIN 2=function 1, PIN 3=function 2 and
PIN 4=function 6
www.ditel.es
Input 1: +00.000 Display 1: +00.000
Input 2: +10.000 Display 2: +10.000
Filter P: 0
Round 01
Tare mode: 1
Brightness: High
Setpoint 1: +01.000, Setpoint 2: +02.000
Setpoint 3: +03.000, Setpoint 4: +04.000
Compared with: Net
Mode: HI
Dly: 00.0
Alarm Color: No Change
Display HI: +10.000
Display LO: +00.000
key sequentially for each one of the setpoints values
MICRA-M
82

Publicité

loading