Type 2030, 2031, 2031 K, 2032,
2033, 2037
→
Align diaphragm.
Observe mark tab for direction of flow!
→
Place actuator back on the housing.
→
Lightly cross-tighten the housing screws until the diaphragm is between the housing and actuator.
do not tighten the screws yet.
→
Actuate the diaphragm valve twice to position the diaphragm correctly.
→
Without applying pressure, tighten the housing screws to the permitted tightening torque (see
torques for diaphragms).
→
Pressurize lower control air connection with compressed air (value as indicated on the rating plate).
→
Check the tightening torque of the screws again.
replacement of the diaphragm for control functions B and i
→
Clamp the valve housing in a holding device.
(applies only to valves not yet installed).
→
Loosen the fastening screws crosswise and remove actuator together with diaphragm from the housing.
→
Unbutton or unscrew old diaphragm. If attachment is with a bayonet catch, remove the diaphragm by rotating
it through 90° (see Table 8:Fastening types for diaphragms).
→
Install new diaphragm in actuator (see
→
Align diaphragm.
Observe mark tab for direction of flow!
→
Place actuator back on the housing.
→
Lightly cross-tighten the housing screws without pressurization until the diaphragm is between the housing
and actuator.
do not tighten the screws yet.
→
Pressurize upper control air connection with compressed air (value as indicated on the rating plate) (see
Figure 15: Control air connection).
→
Actuate the diaphragm valve twice.
→
Tighten the housing screws to the permitted tightening torque (see
diaphragms).
Control air connection
Figure 18:
Repairs
Table 8:Fastening types for diaphragms).
Table 7: Tightening torques for
Upper control air connection
(for CFB and CFI)
Lower control air connection
(for CFA and CFI)
Table 7: Tightening
english