ETTING THE ALARMS
Select Alarms in the installer menu.
CI dosing alarm – only for technopool3 pH/ClJ
This is a dosing alarm and if the CI pump doses the product and there is no variation in CI (2.5% of the value set in
ppm CI Max) during the set time, the system signals the alarm and stops dosing.
The alarm is automatically disabled when the setpoint is neared (when the difference between the CI measure and
the setpoint is less than 2.5% of the value set in ppm Cl Max).
Use the ▼▲ keys to set the desired value or disable the alarm (Off) and then confirm with the Enter key.
The time values that can be set are 5÷60 minutes.
HP dosing alarm – only for technopool3 pH/HP
This is a dosing alarm and if the HP pump doses the product and there is no variation in HP (1% of the value set in
ppm HP Max) during the set time, the system signals the alarm and stops dosing.
The alarm is automatically disabled when the setpoint is neared (when the difference between the HP measure and
the setpoint is less than 10% of the value set in ppm HP Max).
Use the ▼▲ keys to set the desired value or disable the alarm (Off) and then confirm with the Enter key.
The time values that can be set are 5÷60 minutes.
Buzzer
Activates or deactivates the alarm acoustic signal.
Press keys ▼▲ to select the two options and Enter to confirm.
Out 24V Alarm
Sets the operation mode of Out 24V output, which can be set either open or closed, when alarms occur.
Press keys ▼▲ to select the two options and Enter to confirm.
ADSP7000570
Contr. Dos. (V1)
Enables or disables the dosing, when signal V1 occurs (signal of the
active recirculation pump).
Press keys ▼▲ to select the two options and Enter to confirm.
Flow control
Enables or disables the dosing, when water flow occurs.
Press keys ▼▲ to select the two options and Enter to confirm.
pH dosing alarm
This is a dosing alarm and if the pH pump doses the product and there is
no variation in pH (0.05 pH) during the set time, the system signals the
alarm and stops dosing.
The alarm is automatically disabled when the setpoint is neared (when the
difference between the pH measure and the setpoint is less than 0.2 pH).
Use the ▼▲ keys to set the desired value or disable the alarm (Off) and
then confirm with the Enter key.
The time values that can be set are 5÷60 minutes.
Rx dosing alarm – only for technopool3 Time/pH/Rx and pH/Rx
This is a dosing alarm and if the Rx pump doses the product and there is
no variation in Rx (5 mV) during the set time, the system signals the alarm
and stops dosing.
The alarm is automatically disabled when the setpoint is neared (when the
difference between the pH measure and the setpoint is less than 20 mV).
Use the ▼▲ keys to set the desired value or disable the alarm (Off) and
then confirm with the Enter key.
The time values that can be set are 5÷60 minutes.