TECHNOPOOL3
Dosing systems for swimming pools
4.9
S
ETTING THE SOLENOID VALVE
The operation mode of the control relay of the solenoid valve can be ON/OFF or cyclical.
ON/OFF: The relay opening and closing is controlled by the redox/chlorine/hydrogen peroxide reading; if the
system reads a value lower than the set Setpoint, then the relay is activated (ON), otherwise it is deactivated
(OFF). In this case, a hysteresis of 10 mV (redox, Rx), 0.05 ppm (chlorine, ClJ) or 5 ppm (hydrogen peroxide, HP)
must be considered.
Cyclical: The relay opening and closing is continuously controlled by the On and OFF timing, which can be
proportional to the temperature (set on automatic or manual) or not (temperature set on OFF).
Manual temperature or with PT100:
Temperature OFF (disabled):
Enter the installer menu, select option Set Point/Timer , press key Enter and then key F more than once, until
Relay On is displayed:
Temperature OFF (disabled):
ADSP7000570
Relay On – Relay On T. Max – Relay Off – Relay Off T. Max
Relay On – Relay Off
Relay On
It indicates the relay ON schedule (solenoid valve open).
Press keys ▼▲ to set the desired value and Enter to confirm.
Values that can be set are 0÷59 seconds or 1÷60 minutes.
Relay Off
It indicates the relay OFF schedule (closed solenoid valve).
Press keys ▼▲ to set the desired value and Enter to confirm.
Values that can be set are 0÷59 seconds or 1÷60 minutes.
rev. 1.6
09/01/2014
QUICK PROGRAMMING
ENGLISH
53/136