INTRODUCTION
Door Access
Disconnect power BEFORE making electrical connections. Below is an example of a wiring setup for door access. Door access can
be wired to Relay 1, 2, 3, or 4 on the Door of Control Board. Input and output port functions on CAPXLV2 can be configured via myQ
Community web portal. Below is an example use case of connections to various external devices.
RFID ANTENNA
with Wiegand output
Power for RFID ANTENNA
(Not Provided)
DO NOT use the power
NOTE: For the LiftMaster RFID
reader, follow the wiring diagram
supply for the controller
in the manual for the LMSC1000.
SUPERVISED (DOOR STATUS)
DOOR SENSOR
(SUPERVISED)
EOL (End of Line) Resistor
(1k ohm)
*PRIMARY RELAY
Use 18-22 AWG
For DC Power:
Install a 1N4005
diode or equivalent
Use 18-22 AWG
For DC Power:
Install a 1N4005
diode or equivalent
ACCOUNT SETUP
WIEGAND
KEYPAD
OR
DOOR SENSOR
OR
(NON-SUPERVISED)
For AC Power:
DOOR STRIKE
Install a Siemens
S10K30MOV
(Metal Oxide Varistor)
(provided) or equivalent
Power for Door Strike
(Not Provided)
COMMON
+
NORMALLY OPEN
OR
MAGLOCK
For AC Power:
Install a Siemens S10K30MOV
(Metal Oxide Varistor) (provided)
or equivalent
NORMALLY CLOSED
COMMON
+
Power for Maglock
(Not Provided)
DO NOT use the power
supply for the controller
POWER
NETWORK/MOUNTING
READER
OR
NOTE: For KPR2000
keypad, wire the pink and
black (ground) wires together.
REQUEST TO EXIT
PROXIMITY
PUSH
SENSOR
BUTTON
OR
REQUEST TO EXIT
SUPERVISED
NORMALLY OPEN
NORMALLY CLOSED
NORMALLY OPEN
AUXILIARY RELAY
Low
Voltage
Power
Supply
Isolation
Relay
NOTE: DO NOT
run high voltage
power within
the CAPXL
enclosure.
ALARM BYPASS
COMMON
NORMALLY OPEN
19
ACCESS CONTROL
NOTE: The length of the unshielded
wires should be kept to a minimum to
avoid electrical noise.
NOTE: When wiring
a LiftMaster Smart
Reader, follow the
wiring diagram
colors in the
Smart Reader
install guide.
Do not use the
color guide here.
COMMON
COMMON
COMMON
LIGHT
LOAD
LINE
OR
* NOTE: MAGLOCK, door strike
and ALARM BYPASS not
evaluated by UL.