Electrical Installation; Location And Troubleshooting; Maintenance And Service Instructions; Maintenance Schedule - stayer GID1000 Instructions D'emploi

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 30

4.7 Electrical installation

The electrical system will be mandatory for attesting
authorized in writing their work.
Connections for standby power to a building's electrical
system must be made by a qualified electrician and must
comply with all applicable laws and electrical codes.
Improper connections can allow electrical current from the
generator to back feed into the utility lines. Such back feed
may electrocute utility company workers or others who
contact the lines during a power outage, and when utility
power is restored, the generator may explode, burn, or
cause fires in the building's electrical system.
To prevent electrical shock from faulty appliances, the
generator should be grounded. Connect an electric
conductor (cable) of at least 1.5mm² between the
generator's ground terminal and an external ground
source.
Limit operation requiring maximum power to 30 minutes.
For continuous operation, do not exceed the rated power. In
either case, the total wattage of all appliances connected
must be considered.
Do not exceed the current limit specified for any one
receptacle.
Do not modify or use the generator for other purpose than it
is intended for. Also observe the following when using the
generator:
- Do not connect generators in parallel.
- Do not connect an extension to exhaust pipe.
- When an extension cable is required, be sure to use a
rubber sheathed flexible cable.
- Limit length of extension cables: 60m for cables of 1.5mm
and 100m for cables of 2.5mm .
- Keep the generator away from other electric cables or
wires such as distribution network.

4.8 Location and Troubleshooting

Engine will not start:
Enough fuel?
Yes
Are the engine switch and fuel
valve "on"?
Yes
Enough lubricating oil?
Yes
Is there fuel in the carburetor?
Yes
NO
Spark plug works or
Replace spark plug.
not?
Shake the generator several times to make the float rise if
the generator cannot start after adding oil for the first time
and the oil alarm indicator stays on when pulling the starting
grip.
Make sure there is no spilled fuel around the spark plug.
Spilled fuel may ignite.
If the engine still doesn't start, have the generator repaired
by a licensed repair person.
2
NO
Add fuel.
NO
Turn them to the "on" position.
NO
Add more qualified oil.
Start a few times to ensure that
NO
fuel enters the carburetor.
NO
Send the generator
to an authorized dealer
ENGLISH
25
Inspection:
- Remove the spark plug rubber boot and clean any dirt from
around the spark plug.
- Remove the spark plug and place it in the spark plug
rubber boot.
- Connect the side electrode of the spark plug to the metal
parts of the engine.
- Pull the starting cord. A spark could jump across the gap.
The equipment that connects generator doesn't start:
Is the output indicator on?
NO
Is the overload
indicator on?
Yes
Does the electrical equipment
work when plugged in directly?
There is no power in the direct current electric outlet:
Is the electric
circuit breaker intact?

5. Maintenance and service instructions

5.1

Maintenance Schedule

2
The purpose of the maintenance and adjustment schedule
is to keep the generator in the best operating condition.
Inspect or service as scheduled in the table below.
Shut off the engine before performing any
maintenance. If the engine must be run, make
sure the area is well ventilated. The exhaust
contains poisonous carbon monoxide gas.
Use authorized parts or their equivalent. The use
of replacement parts which are not of equivalent
quality may damage the generator.
Maintenance Schedule
Regular Service Period (1)
Item
Perform at every indicated month or operating hour
interval, whichever comes first.
Engine oil
Air cleaner
Spark plug
Spark arrester
Valve clearance
Fuel tank and filter
Fuel line
25
Send the generator to an
NO
authorized dealer.
Restart after turning off the
NO
overload indicator.
Yes
Send the generator to an
authorized dealer.
Yes
Replace the electric equipment.
Repair the electric equipment.
NO
Replace the electric circuit breaker.
Yes
Send the generator to
an authorized dealer.
Check level
Change
Check
Clean
(2)
Check-adjust
Clean
Check-adjust
Clean
Check
Every 2 years (Replace if
necessary) (3)
(3)
(3)

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Gid1400Gid2200Gav2800Gav5500eGav7500e

Table des Matières