2. Installation location
en
Fig. 2-4
4
(mm)
Fig. 2-3
(A)
Fig. 2-5
(B)
Fig. 2-6
2.3. Outline dimensions (Outdoor unit) (Fig. 2-3)
2.4. Ventilation and service space
2.4.1. Windy location installation
When installing the outdoor unit on a rooftop or other location unprotected from the
wind, situate the air outlet of the unit so that it is not directly exposed to strong winds.
Strong wind entering the air outlet may impede the normal airflow and a malfunction
may result.
The following shows three examples of precautions against strong winds.
(1) Face the air outlet towards the nearest available wall about 500 mm away from
the wall. (Fig. 2-4)
(2) Install an optional air protection guide if the unit is installed in a location where
strong winds from a typhoon, etc. may directly enter the air outlet. (Fig. 2-5)
(A) Air protection guide
(3) Position the unit so that the air outlet blows perpendicularly to the seasonal wind
direction, if possible. (Fig. 2-6)
(B) Wind direction