Télécharger Imprimer la page

Sew Eurodrive MOVITRAC LTP-B Notice D'exploitation page 31

Masquer les pouces Voir aussi pour MOVITRAC LTP-B:

Publicité

Branch Circuit Protection
Devices
0008
0015
0022
Devices
0008
0015
0022
0030
0040
0055
0075
0110
0150
0185
0220
0300
0370
0450
0550
0750
Devices
0008
0015
0022
0040
0055
0075
0110
0150
0185
0220
0300
0370
0450
0550
0750
0900
1100
1320
1600
2000
2500
1 × 200 – 240 V devices
Non semiconductor fuses
(currents are maximum values)
15 A
17.5 A
25 A
3 × 200 – 240 V devices
Non semiconductor fuses
(currents are maximum values)
10 A
15 A
17.5 A
30 A
30 A
35 A
40 A
70 A
80 A
90 A
125 A
150 A
200 A
225 A
250 A
300 A
3 × 380 – 480 V devices
Non semiconductor fuses
(currents are maximum values)
6 A
10 A
10 A
15 A
25 A
30 A
35 A
45 A
60 A
70 A
80 A
100 A
125 A
175 A
200 A
250 A
300 A
300 A
400 A
500 A
600 A
Installation électrique
Consignes d'installation
Max. supply short
Max. line voltage
circuit current
100 kA rms (AC)
Max. supply short
Max. line voltage
circuit current
100 kA rms (AC)
Max. supply short
Max. line voltage
circuit current
100 kA rms (AC)
Notice d'exploitation – MOVITRAC
5
240 V
240 V
480 V
31
®
LTP-B

Publicité

loading