RCD type (F2):
sinusoidal test current
pulsating test current
selective (delayed) RCD
For testing selective RCDs, measurement starts after a time delay of 30 seconds.
(F3):
RECALL function; the measured values of the last AUTO measurement are shown on the digital display
each time a key is pressed.
I∆N nominal fault current (F4):
Press the function key F4 to select the nominal fault current:
Available nominal fault currents (sinusoidal testing current)
-
Connect the measuring leads to the BENNING IT 105 as shown in figures 4 or 5 and apply them to the
test object.
-
Press the TEST key 4 to start the measurement.
-
Switch the RCD on again after each tripping until the test sequence is completed.
-
Press the function key F4 3 to call the tripping times of the different nominal fault currents on the main
display K.
8.6.2
Tripping time RCDt (x½, x1, x5)
-
Use the rotary switch 1 to select the multiplier (x½ J, x1 K, x5 L) of the testing current for the desired
function RCDt.
-
The symbols of the function keys F1 A to F4 D are briefly shown on the digital display 2 . You can
use the function keys F1 to F4 3 to make the following settings:
F1
0° / 180°
04/ 2020
►
►
½ x I∆n at 0°
▼
½ x I∆n at 180°
▼
I∆n at 0°
▼
I∆n at 180°
▼
5 x I∆n at 0°
▼
5 x I∆n at 180°
▼
Start of AUTO
measurement
►
10 mA
30 mA
F2
BENNING IT 105
►
:
►
100 mA
F3
–
F4
I∆N
25