8.5 Loop impedance (Z
Measurement requires correct connection of the mains voltage to the BENNING IT 105 as
shown in figures 4, 5 or 6. The mains voltage indicator must light permanently:
If the mains voltage indicator flashes, check the measuring leads for correct connection or turn the shock-
proof plug of the test cable by 180°.

8.5.1 Measurement with high test current (HIGH CURRENT)

Measuring the loop impedance Z
RCD! If the RCD trips, "RCD" is indicated on the digital display 2 and measurement will
be interrupted.
-
Select the desired function Z
-
The symbols of the function keys F1 A to F4 D are briefly shown on the digital display 2 . You can
use the function keys F1 to F4 3 to make the following settings:
F1
L-PE / L-N
L-PE or L-N (F1):
It is possible to determine via the function key F1 3 , whether measurement shall be carried out between
L-PE (loop impedance Z
AUTO start (F4):
With the Auto start function being enabled, measurement will be started 4 seconds after the BENNING IT 105
has been connected to the mains voltage. Press the function key F4 3 again to disable the function.
-
Connect the measuring leads to the BENNING IT 105 as shown in figures 4, 5 or 6 and apply them to
the test object.
-
Press the TEST key 4 to start the measurement.
-
The main display K shows the loop impedance (Z
shows the prospective fault current (PFC)/short-circuit current (PSC).
Note:
For measuring the loop impedance Zs (L-PE) on three-phase loads without neutral conductor (e. g.
motors), the green measuring lead jack PE/L2 6 and the blue measuring lead jack N/L3 7 can be bridged
via the blue 4 mm adapter.
The measurement of the line impedance Z
current. For this, connect the measuring leads to the BENNING IT 105 as shown in figure 6 and apply
them to the test object. If the green measuring lead socket PE 6 is not connected to ground PE of the
test object, after pressing the TEST key 4 the symbol "NO-E" is displayed in the digital display 2 and the
measurement is blocked.
8.5.2

Measuring with a low testing current (NO-TRIP)

Measuring the loop impedance (Z
an upstream RCD! However, existing fault currents in the installation might influence the
measurement. If the RCD trips, "RCD" is indicated on the digital display 2 and measure-
ment will be interrupted.
-
Select the desired function Z
-
The symbols of the function keys F1 A to F4 D are briefly shown on the digital display 2 . You can
use the function keys F1 to F4 3 to make the following settings:
F1
L-PE / L-N
04/ 2020
) and line impedance (Z
S
(L-PE) with a high testing current will trigger an upstream
S
/Z
(HIGH CURRENT) G with the rotary switch 1 .
S
I
F2
) or L-N (line impedance Z
S
(L-L), phase to phase, can only be performed with a high test
I
) L-PE with a low testing current normally will not trigger
S
/Z
(NO TRIP) H with the rotary switch 1 .
S
I
F2
BENNING IT 105
)
I
F3
).
I
)/line impedance (Z
S
F3
F4
AUTO
) and the secondary display J
I
F4
AUTO
23