4. INSTALLATION INSTRUCTIONS
4.4.1. Mounting the Product
22 3/16"
- Fix the mounting bracket to the wall (
563mm
- Hang the product on the bracket (
- Check that the product is stable and horizontal.
- Use the mounting bracket supplied with the product to secure it in place. Use a wall plug (not supplied) (
4.5. Installation on Feet (Accessory)
16 3/4"
425,75mm
The unit can be installed on the floor using an accessory floor stand. The unit must be accessible for maintenance.
- Assemble the stand according to the instructions supplied.
- Check that the unit is securely supported by the feet.
- Refer to the instructions supplied with the accessory for further details.
22 3/16"
22 3/16"
563 mm
563mm
16 3/4"
16 3/4"
425.75 mm
425,75mm
4.6. Connecting Ventilation Ducts from the Unit
To ensure optimum sound levels, we recommend a straight duct length of at least 50 cm at the unit outlet. Elbows are not recommended.
4.7. Electrical Connections
Connect the unit to the connector under the electrical box, using a cable directly connected to the
installation's electrical panel.
Mains: 230 V single-phase alternating current. Characteristics and installation requirements for power
cable (not supplied).
- Cable cross-section: 3 x 1.5 mm
- The ground wire must be longer than the others (the last wire to be disconnected in the event of a pull).
Stripping length: 10 mm.
The installer must check that the wires are correctly inserted into the connector each time.
The installation will include :
- A two-pole circuit breaker
Connection to the terminal block installed on the product. Be sure to observe the connections and
polarities marked on the connector.
4.8. Electronic Connections
View of electronic board customer connections :
X1
X2
X3
L
N
A
19
22 3/16"
) (the cardboard packaging includes a template for drilling the wall to the correct dimensions).
563mm
1
+
).
2
1
10 5/8"
269,57mm
22 3/16"
22 3/16"
563 mm
563mm
10 5/8"
10 5/8"
269,57mm
269.57 mm
7 1/16"
179,56mm
179.56 mm
7 1/16"
179,56mm
minimum (maximum 2.5 mm
with insulated end ferrule or 4 mm
2
2
X4
X5
X6
B
A
B +V USB +24V +
9 1/8"
7 1/16"
232,40mm
2 mm
9 1/8"
232,40mm
).
2
X7
X8
X9-X12
-
AI0 AI1 AO0
).
3
9 1/8"
Location
Function
X1
230V power supply
Accessory not available
X2
in North America
X3
Modbus customer connection
X4
Remote control connection
X5
USB connection
X6
IBus connection
X7
Dry contact connection
X8
Dry contact / NO default
0-10V inputs/outputs
X9: Analog input 0
X10: Analog input 1
X9-X12
X11: Analog output
Dry contact / NO default:
X8 X12
1
2
3
X12 :
230V